Skip to main content

Which side of the transformer is primary and which side is secondary?

From the transformer manufacturer’s perspective, the side on the transformer that is initially energized should be considered primary. HPS solar duty transformer identifies the primary side on its nameplate. Energizing the transformer from the secondary side may cause elevated energizing inrush currents that can cause nuisance faults.

  • Which side of the transformer is primary and which side is secondary?

      Category:

      Tags: FAQ, Solar Power

      From the transformer manufacturer’s perspective, the side on the transformer that is initially energized should be considered primary. HPS solar duty transformer identifies the primary side on its nameplate. Energizing the transformer from the secondary side may cause elevated energizing inrush currents that can cause nuisance faults.

  • Do I need a Wye-N connection to supply my solar inverter if it does not need or check for a balanced phase to ground voltage?

      Category:

      Tags: FAQ, Solar Power

      Suggested to use a wye-N connection to supply the inverter which does not check for a balanced phase to ground voltage.

       

       

  • What is IEEE 519-2014

      Category:

      Tags: power quality

      IEEE is the Institute of Electrical and Electronics Engineers. IEEE 519-2014 is a document that establishes levels of voltage and current harmonic distortion acceptable to the distribution system based on the input transformer characteristic and the loads on a customer’s facility. Many electrical consultants are including compliance with IEEE 519-2014 in their design specifications to help reduce harmonic problems and avoid penalties that can be imposed by electrical utilities. More information about the levels of harmonics can be found on the IEEE website.

      • The IEEE 519-2014 also outlines the Point of common coupling (PCC) as the point where the utility meets the facility
      • The current and voltage harmonic limits set by IEEE and followed by many specifiers are clearly outlined in the following IEEE tables shown below:

      Voltage Distortion Limits & Maximum Harmonic Current Distortion

  • Does the VFD have to be equipped with a DC link choke to work with Active Harmonic Filter

      Category:

      Tags: power quality

      All non-linear loads should have an input line reactor a minimum 3% impedance or a DC link choke (minimum 4% impedance) to achieve desired system performance.

  • What is an active harmonic filter?

      Category:

      Tags: power quality

      Due to the increasing usage of non-linear loads such as VFDs, harmonics are being introduced into the power grid which is contributing to poor power quality and leads to overheating of equipment and nuisance faults. Active Harmonic Filters are parallel devices that are used to mitigate harmonics to the levels defined by IEEE-519.

      HPS TruWave AHF utilizes high frequency current sensors to continuously monitor the load and harmonic currents. By utilizing highly sophisticated software and a powerful DSP microcomputer, the system is able to instantaneously inject a corrective current from its IGBT based inverter to dramatically reduce harmonic distortion. The corrective current is equal to but 180 degrees out of phase with the existing harmonic currents to cancel their effect.

      Active filters work on the same principle s as noise cancelling head phones except they cancel harmonic currents and reduce distortion.

  • What are the benefits of an active filter over a passive filter

      Category:

      Tags: power quality

      Here are some of the advantages that Active Harmonic Filters can provide over the Passive Filters.

      • Active Harmonic Filters provide far superior flexibility and performance over passive filters.
      • Not all Passive filters can achieve the 8% or 5%THD IEEE-519 specification even at full load. The HPS TruWave AHF will achieve less than 5% THD even until 10% loaded. Passive filters typically provide less overall mitigation as the load decreases.
      • AHF will not cause a leading power factor at no load while passive filters do
      • AHF can be installed anywhere in the lineup, while the passive filters must be installed at each VFD
      • Active filters are cost and space effective with the use of multiple VFD loads compared to passive filters

  • Do I need to use a line reactor with VFDs to work with an Active Harmonic Filter

      Category:

      Tags: power quality

      All non-linear loads must have an input line reactor (minimum 3%) or a DC link choke to achieve the desired system performance. While an AHF can correct harmonics without line reactors, issues can occur if there is not sufficient impedance between an AHF and a load.

      Using line reactors is also cost effective since reactors mitigate some of the harmonics and a smaller AHF can be deployed.

  • Can I use Active Harmonic Filter for single phase loads

      Category:

      Tags: power quality

      An active harmonic filter cannot be used to correct harmonics from single-phase harmonic sources. AHF’s correct the harmonics from three-phase sources and therefore are also only designed to run on three-phase systems.

      Isolation transformers and line reactors can mitigate some of these harmonics from single-phase sources. Three-phase system with large loads of single-phase harmonic sources can also use Harmonic Mitigating Transformers (HMT).

  • Can I use PFCC with Active Harmonic Filters

      Category:

      Tags: power quality

      Power Factor Correction Capacitors can be used on systems with AHF’s. AHF’s harmonic mitigation may even be required to protect PFCC from excessive heating and failure caused by harmonics. PFCC cannot be installed on the load side of AHF current sensors. PFCC should be installed between the AHF and the utility point of common coupling (PCC).

  • Can and Active Harmonic Filter improve power factor

      Category:

      Tags: power quality

      Yes, an AHF can be used to correct the Power Factor to near unity. However, using a combination of an AHF and Power Factor Correction Capacitors is often a more economical solution.

  • How many CT do I need to use for the Active Filter

      Category:

      Tags: power quality

      CT’s are used with the HPS TruWave AHF to continuously monitor the load and harmonic currents. Typically, if the system only has three-phase loads downstream to the AHF, two CT’s can be used; the TruWave software will calculate the third phase current. If the system has any single-phase loads, a third CT is required.

      Here are some the installation considerations for the current transformers (CT’s) with the AHF:

      • Must be located upstream of VFD loads requiring correction
      • Two CT’s are required for the correction of three-phase loads
      • A third CT is only required if there are also single-phase (line to neutral) loads
      • The CT’s are sized based on the current rating of the bus

  • What are the main functions performed by an Active Harmonic Filter

      Category:

      Tags: power quality

      The two main functions performed by AHF are:

      • Harmonic Mitigation
      • ower Factor Correction

  • What does AHF stand for
  • What communication options come with the HPS TruWave Active Harmonic Filter

      Category:

      Tags: power quality

      Standard: Ethernet

      Optional: Ethernet/IP & Modbus TCP

  • Which applications are best addressed by an Active Harmonic Filter

      Category:

      Tags: power quality

      AHF’s are used where a significant portion of the load consists of VFD’s or other three-phase non-linear sources such as large three-phase DC power supplies, electric vehicle chargers or UPS’s. VFDs are defined as non-linear loads which generates an enormous amount of harmonics in a system. Harmonics cause a host of electrical problems. AHF’s are great candidates to mitigate harmonics from a system where multiple VFD loads that represent a significant portion of the total load.

      Active filters are designed to reduce harmonics from three-phase sources. For single-phase harmonic sources, solutions such as harmonic mitigating transformers should be considered.

  • What information is needed to size an Active Harmonic Filter

      Category:

      Tags: power quality

      The following information is all required in order to correctly size an active harmonic filter:

      • One-line diagram of the system. Location and size of VFD’s and Power Factor Correction Capacitors is very useful.
      • Detailed equipment lists can also be used, especially in conjunction with one-line diagrams.
      • VFD information: Horse Power or Current size.
      • Are line reactors being used with each VFD? If so what is the impedance?
      • Will the active filters operate on generator?
      • Are there any large soft start loads located downstream of the AHF?
      • Local Environmental Conditions

  • What information does the TruWave Active Harmonic Filter display give

      Category:

      Tags: power quality

      The display presents valuable information including:

      • Line Power
      • Line current
      • Line Voltage
      • Line Frequency
      • Harmonics % generated by the VFD system
      • Harmonics % corrected by the AHF

      For more detailed info refer to the HPS TruWave AHF user manual.

  • What Output Problems Can Occur with Variable Frequency Drives (VFD or VSD) and How Can You Mitigate These Issues?

      A voltage-sourced Variable Frequency Drive (VFD) uses Insulated-Gate Bipolar Transistors (IGBTs) to rapidly switch voltage on and off to form a Pulse Width Modulated (PWM) voltage source for the motor. The PWM simulates a sine wave voltage source to the motor and it operates as if it was being powered by a sine wave.  The PWM wave allows the VFD to change the fundamental frequency of the PWM waveform and simulate sine waves.  Since the speed of a motor is directly related to the fundamental frequency of the sine wave, a VFD can control speeds from a fraction of a hertz to hundreds of hertz.

      Output reactors, dV/dT filters or drive isolation transformers can be used to help mitigate some issues caused by the PWM output.  PWM outputs cause rapid switching transitions which can cause over-voltages due to parasitic capacitance and inductance in the motor’s leads. The parasitic currents and voltages can be determined by the equation of V = L × (Δi/Δt).  VFD’s switching frequencies (the amount of pulses used to simulate the sine wave) generally range from 1,000-20,000 pulses per second.  IGBT’s produce an almost perfect square wave which produces a very high Δv/Δt.   High Δv/Δt can cause higher surge currents in the leads. This then causes high voltage pulses across the parasitic inductances.  Therefore the faster the pulses switch, the greater the impact of cable capacitance and inductance. These voltage pulses stress the motor’s windings causing higher audible noise, heat and possibly premature failure of the insulation. There is also capacitance in the motor’s bearings.  The combination of lubrication and air gaps prevent direct and continuous contact of the bearings to the metal traces that contain them.  Parasitic currents [I = C × (Δv/Δt)] causes current to flow through the bearings.  The amount of current will increase as the VFD output switching speed increases. These currents can cause micro pits to form in the bearings and eventually will lead to premature bearing failure.

  • What is ANSI NETA ATS-2017?

      A recommended standard for independent testing of an electrical system in a structure such as a hospital, data center or laboratory. In addition to the transformers, this standard could be applied to switchgear, cables, instrumentation and metering devices, motors including VSD’s and emergency systems.

  • common transformer installation issues

      Category:

      Tags: power factor

      Improper Secondary Ground
      If the secondary of the transformer is not grounded properly, the output voltage will look ok between the phases but it will float and not be referenced to earth ground.

      Back-Feeding Delta Primary/Wye Secondary Transformers
      While a base wye secondary transformer can be field modified to backfed, the field modifications may violate U.L., NEC or local code and the transformer’s warranty. Don’t back-feed delta/wye transformers.

      Back-Feeding Transformers above 1 kVA
      Back feeding larger transformers can result in high inrush currents upon transformer energization and nuisance tripping of circuit breakers and fuses. Due to a number of factors which affect inrush, this issue is difficult to predict and costly to fix. The best way to handle this is to purchase transformers wound as step-up. If this isn’t feasible, transformers should be sized to the maximum amperage protection allowed by code, the larger the transformer, the more potential for this to occur.

      Power Wires Routed over the core and coils
      The are being ventilated through the core and coils can be very hot, in excess of 100oC. This can cause wire insulation failure.

      Power Wires terminated in the bottom of the transformer compartment
      Conduit should not be terminated in the bottom of the transformer with a grated floor. The grated floor is needed to provide airflow to cool the transformer but the grates provide a poor surface to mount a coupling and may also violate NEC code.

      Missing Vibration Pads or Vibration Isolators
      All transformers vibrate at 120 hz because of the electromagnetic field in the core. These vibrations and audible noise can transfer through the floor, vibration pads and isolators help to minimize this issue in commercial applications.

      Missing Drip Shields
      While all outdoor applications need a minimum of a NEMA 3R enclosure, even indoor applications near sprinklers would require a minimum NEMA 2S enclosure and therefore drip shields.

      Transformer Harmonic Heating
      Due to the prevalence of non-linear loads and the harmonics they produce, transformers can overheat if not specified properly. As a rule of thumb, if a load contains 25-50% non-linear sources, use K=4, if a load exceeds 50% non-linear sources use K=13.

      Transformer Ambient Heating
      Transformers need to be placed in locations that allow proper ventilation to remove the heat they produce during normal operation.

      More troubleshooting

  • What are some of the solutions to Dirty Power?

      Category:

      Tags: dirty power

      The solutions are as wide ranging as the problems. So are the prices. This Table summarizes some solutions and their price ranges.

      Table for dirty power

      Unfiltered Surge Fuses are very inexpensive, and may provide damage protection from lightning strikes or other surges, but they do not filter out adverse noise.

      Filtered Surge Suppressors are inexpensive solutions to noise suppression and surge protection. The better units inhibit surges above 5000 volts, 200 amps. They should also provide noise filtration of 10dB or more to cover average power disturbances.

      Computer Regulators or Line Voltage Conditioners protect equipment from both noise and voltage fluctuations. They are an inexpensive solution, available in both portable and hardwired models. They provide ideal protection in high noise areas where voltage fluctuations exceed the regulating range of the computers power supply.

      Super Isolation Transformers provide inexpensive protection against frequency variation or noise related disturbances. This is adequate where voltage fluctuations are not a serious problem. Most high-end computers have built-in voltage regulation, but still require protection from line noise.

      U.P.S. Systems are in effect self-contained power centers. They provide backup power for a period of time when utility power is interrupted. Most U.P.S. systems also provide noise filtration and surge suppression.

  • How do you choose the correct, most cost-effective Clean Power Solution?

      Category:

      Tags: clean power

      Not everyone has the same power problem. Finding the most cost-effective solution requires some analysis of your equipment, the power system and the available solutions in the market. The table below lists causes and effects of many common power problems. You or your electrician can determine the most likely cause of power problems based on knowledge of your location, the kinds of equipment you operate in that location, and the kind of power distribution system in your building.

      The following table lists the types of Clean Power products available from HPS to solve your power problems.

      Table for clean power

       

      HPS offers the following products for clean power solutions:

       

  • How do you properly size a distribution transformer?

      Distribution transformers need to take several items into consideration when sizing including:

      • Maximum Load
      • Potential future load growth (typical is 25%)
      • Load Inrush and voltage regulation
      • Harmonics and Power Factor
      • Ambient Temperature
      • Additional Service Factor

      For reference, NEC Article 210, Branch Circuits, and NEC Article 230, Services is used to select panelboards and the size of branch circuits. Typically a transformer must be sized to support the load requirements of the switchgear, panelboards and branch circuits. For drive isolation transformers, it is suggested to take sizing charts provided by manufacturers into consideration due to derating for harmonics. In addition to sizing a transformer, the general types including general purpose, K-Rated, Harmonic Mitigating and Drive Isolation also need to be chosen.

      Distribution transformers are often sized from loads based on NEC Article 220. NEC Article 220.87 does allow transformers to be sized based on peak-load data over a 1-year period. NEC also allows loads to be sized using metered data over 30 days if the additional maximum anticipated heating and/or cooling load is also factored in. This often allows a transformer to be sized lower than the base calculations from NEC Article 220. Peak efficiency for 600V class distribution transformers is typically at 35%. Peak efficiency for medium voltage transformers is typically at 50% load.

      Additional capacity for future loads can be obtained by A) specifying a lower temperature rise (15%-30% for dry type) or B) utilizing fans (25%-50% for dry type).

  • Line reactor – definition
  • Iron core filter reactor – definition
  • What is electrical noise?

      Noise is a very broad term that can be applied to a number of AC power line disturbances. Lightening surges or any other sudden changes in load, such as switching motor loads or power factor correcting capacitors can produce voltage spikes and ringing. Phase controlled rectifier loads and arcing devices produce continuous noise unless adequately filtered. Noise sources are either common mode, which appears between both sides of a power line and ground or of transverse mode, which appears from line to line. HPS Clean Power products, such as our Computer Regulators remove these noise sources.

  • Air core filter reactor – definition
  • dV/dt reactor – definition
  • What is Dirty Power?

      Category:

      Tags: dirty power

      Dirty power is caused by a number of things. Simply put, dirty power is what causes your radio or telephone to ‘crackle’ during an electrical storm; or what causes ‘snow’ on your TV when someone is using a power tool, sewing machine or other appliances in your house. This dirty power, or electrical noise, is a nuisance when it appears on your radio, TV or telephone. When it gets into your computer, it can cause serious errors; improper readouts, printing problems, or even damage your computers circuit.

  • What is IEEE 1584-2018?

      IEEE 1584-2018 provides mathematical models for designers and facility operators to apply in determining the arc-flash hazard distance and the incident energy to which workers could be exposed during their work on or near electrical equipment.

      It generally indicates that systems with an available short circuit current of 2000 Amps or higher should be assessed for arc-flash potential. A rule of thumb would indicate that most systems fed by a 45 kVA or larger transformer will need to be assessed if impedance (%Z) of 45 kVA is less than 6%, 30 kVA if %Z is less than 4% or 15 kVA if %Z is less than 2%.

  • VAR compensator reactor – definition

      An air core reactor that gets used with solid state circuitries to provide instantaneous reactive power correction to the power grid.

  • What is EMF (Electric and Magnetic Fields)?

      Electric and Magnetic Fields are produced by the distribution of electricity through current-carrying devices.  The extremely low frequency EMF or power frequencies fields 50 to 60 Hz are produced by the generations, transmissions and use electrical energy.

  • What Effects Does EMF (Electric and Magnetic Fields) Have on Equipment?

      Computers, servers, monitors, medical equipment and other complex electronic equipment can all be affected by the presence of EMF fields. These fields have been known to distort monitors, cause faulty readings, computer errors and even equipment lock-ups.

  • Why do non-linear loads have low power factors and why is it important to have a high power factor?

      Category:

      Tags: power factor

      Power factor is a measure of how effectively a specific load consumes electricity to produce work. The higher the power factor, the more work produced for a given voltage and current. Figure 3-1 shows the power vector relationships for both linear and non-linear loads. Power factor is always measured as the ratio between real power in kilowatts (kW) and apparent power in kilovolt-amperes (kVA).

      For linear loads, the apparent power in kVA (S = V•I) is the vector sum of the reactive power in kVAR (Q) and the real power in kW (P). The power factor is P/S = CosΦ, where Φ is the angle between S and P. This angle is the same as the displacement angle between the voltage and the current for linear loads. For a given amount of current, increasing the displacement angle will increase Q, decrease P, and lower the PF. Inductive loads such as induction motors cause their current to lag the voltage, capacitors cause their current to lead the voltage, and purely resistive loads draw their current in-phase with the voltage. For circuits with strictly linear loads (a rare situation) simple capacitor banks may be added to the system to improve a lagging power factor due to induction motors or other lagging loads.

      For non-linear loads, the harmonic currents they draw produce no useful work and therefore are reactive in nature. The power vector relationship becomes 3 dimensional with distortion reactive power, H, combining with both Q and P to produce the apparent power which the power system must deliver. Power factor remains the ratio of kW to kVA but the kVA now has a harmonic component as well. True power factor becomes the combination of displacement power factor and distortion power factor. For most typical nonlinear loads, the displacement power factor will be near unity. True power factor however, is normally very low because of the distortion component. For example, the displacement power factor of a personal computer will be near unity but its total power factor is often in the 0.65 – 0.7 range. The best way to improve a poor power factor caused by non-linear loads is to remove the harmonic currents.

      Most Utilities charge their customers for energy supplied in kilowatt-hours during the billing period plus a demand charge for that period. The demand charge is based upon the peak load during the period. The demand charge is applied by the utility because it must provide equipment large enough for the peak load even though the customer’s average power may be much lower. If the power factor during the peak period (usually a 10 minute sliding window) is lower than required by the utility (usually 0.9), the utility may also apply a low PF penalty charge as part of the demand charge portion of the bill.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What are Static VAR Compensators (SVCs)?
  • What are Static Synchronous Compensators (STATCOMs)?
  • What is Series Compensation?

      Widely used for voltage correction on longer high-voltage alternating current transmission lines.

  • What is Power Factor or True Power Factor?

      Category:

      Tags: power quality

      The ratio of real power to apparent power and is:  PF = (Power actually delivered to load) ÷ (RMS Voltage x RMS Current).  Waveform distortion caused by harmonics is included in this calculation.  The worse the phase shift between voltage and current and/or the worse the harmonic distortion, the worse the power factor.  Low power factor cause by either harmonic currents (and a distorted sine wave) or reactive power can increase transformer heating.  If PF is low but DPF is not, adding power factor correction capacitors may not help

      Displacement power factor (DPF) is different.  DPF is the cosine of phase angle between the current and voltage fundamental sine waves.  Low power factor is typically caused by inductive loads such as motors.  Fundamental power factor only looks at the 60 Hz sine wave and does not take into effect harmonic currents.  DPF is most useful for sizing and measuring the effectiveness of power factor correct capacitors.

      If PF is low but DPF is not, harmonics may be causing the problem and adding power factor correction capacitors may not improve either PF or DPF.  Solutions such as harmonic mitigating transformers or line reactors should be considered.

  • How bad can the Dirty Power problem get?

      Category:

      Tags: dirty power

      One form of dirty power usually called a surge can burn out computer, audio, video or nay other electronic circuitry in seconds. A surge is a high voltage pulse riding the normal power wave. Surges will commonly measure 600 to 2500 volts. Even though they occur for only mille-seconds, this is enough time to melt down circuits.

  • How does Dirty Power affect my electronic equipment?

      Category:

      Tags: dirty power

      Your computer operates by reading electronic impulses. Dirty power contains a great number of random pulses riding on the normally smooth surface of a power wave. As these random pulses enter the circuits, your computer ‘reads’ them as data. This can cause a whole range of problems. You may suddenly get garbled numbers or letters in a readout or printout.

      You could loose files, skip program steps, have trouble loading programs or have connection problems while on the Internet.

  • Why is Clean Power so critical?

      Category:

      Tags: clean power

      Your computer is a delicate electronic instrument. When you use the keyboard, you’re sending a series of tiny electronic impulses through the computers circuits. The computer ‘reads’ these electronic impulses and makes calculations or performs tasks according to your programmed instructions. If the electrical power feeding your computer is smooth and clean, your computer will behave normally. However, if the power fed into your computer is “dirty”, you could be in for many unpleasant surprises.

      Practically all electronic devices are sensitive to fluctuations in voltage, therefore clean power is vital in order to ensure uninterrupted performance of modern-day electronic equipment.

  • Does HPS build secondary unit substation transformers?

      Category:

      Tags: cast coil, VPI

      Secondary Unit Substation Transformers feed low voltage switchgear or switchboards. They typically range from 150 kVA to 2,500 kVA three-phase. The Primary voltage ranges from 2400 VAC to 34,500 VAC and the secondary from 600VAC to 480 VAC. Taps are typically manually changed while the unit is de-energized. The primary connections are typically delta connected while the secondaries are usually wye connected.

      The units are typically installed inside a building and are either dry (VPI) or cast coil because of safety and installation concerns. These units are often connected directly close coupled to the switchgear. HPS can provide both VPI and Cast Coil Secondary Unit Substation Transformers.

  • Can an Active Harmonic Filter be used to protect a specific circuit or machine in a building

      Category:

      Tags: performance

      AHF’s are used to mitigate harmonics in a total circuit. Let’s set up an example. A company has 5 work cells and each is producing 20 amps of harmonics. A sixth work cell is introduced, it’s a different machine and it produces 30 amps of harmonics. Some operational issues on the new sixth machine have been determined to be caused by Power Quality issues. Can an AHF be deployed to just protect the new machine?

      • If the new machine is fed from a dedicated transformer, it’s possible an AHF designed to handle at least 30 amps could be installed to mitigate harmonics on the secondary of the transformer feeding this machine.
      • If all six machines are fed by one large distribution transformer with no other isolation transformers between, then an active filter large enough to handle the entire harmonic amperage ((20 x 5) + 30 = 130 amps) must be installed.

  • Can the TruWave be used on a 600V system

      Category:

      Tags: harmonics

      Typically the TruWave is rated for 480VAC. However, through the use of a 600V to 480V autotransformer between the TruWave and the load, the TruWave can be used on 600V systems. This same setup can also be used on voltages if needed.

  • Can neutral currents such as the 3rd harmonic be reduced by the use of 3rd harmonic blocking filters?

      Category:

      Tags: harmonics

      Some manufacturers are promoting the use of 3rd harmonic (180 Hz) blocking filters for the treatment of high neutral currents caused by non-linear loads such as personal computers. These devices are parallel L-C filters tuned to 180 Hz and are connected in the neutral of 4-wire systems between the transformer secondary and the neutral-to-ground connection.

      Their high impedance to the flow of 3rd harmonic current forces all connected equipment to draw current that does not contain the 3rd harmonic. Although their use will result in a significant reduction in 3rd harmonic current, it is achieved at the risk of rather severe consequences.

      1. The installation raises questions with respect to NEC 2002 compliance. NEC 250.30(A)(2)(a) states that “a grounding electrode conductor for a single separately derived system … shall be used to connect the grounded conductor of the derived system to the grounding electrode…” In addition, “the grounding electrode conductor shall be installed in one continuous length without a splice or joint…” [See NEC 250.64(C)].

      If a simple splice connection is not allowed, then certainly the L-C circuit of the 3rd harmonic blocking filter should not be allowed either. Also, the installation results in an impedance grounded wye system rather than a solidly grounded system. The only reference in NEC that allows for the introduction of impedance between the neutral and the grounding electrode is found in Section 250.36, High-Impedance Grounded Neutral Systems. However, these systems are permitted only at 480V and higher and only if they do not serve line-to-neutral loads. They also require the use of ground fault detectors. None of these requirements is met in the normal application of the 3rd harmonic blocking filter where the loads are primarily 120V, phase-to-neutral connected computer or other power electronic equipment.

      2. Although tuned to 180 Hz, the L-C circuit will introduce some impedance at 60 Hz as well. The consequences are:
      a. Line-neutral short circuit current will be reduced which will limit a circuit breakers ability to clear a line-neutral fault. This can be very dangerous because an uninterrupted fault (commonly referred to as an arcing fault) will often result in an electrical fire.
      b. The neutral point at the transformers wye secondary can shift. This can result in 120V line-neutral voltages that rise and fall unpredictably as the load balance between the phases varies.

      3. High impedance to the flow of 3rd harmonic current will produce voltage distortion in the form of flat-topping – a dramatic reduction in peak to peak voltage. This will:
      a. Significantly reduce the ride-through capability of switch-mode power supplies (SMPS) since the DC smoothing capacitors will not be allowed to fully charge.
      b. Reduce the SMPS DC bus voltage, thereby increasing the current demand the associated I2R losses. Component reliability will be reduced due to higher operating temperatures.
      c. Often cause Single Phase UPS systems to switch to battery back-up.
      d. Force connected equipment to operate without a 3rd harmonic current – an operating mode for which they have not been intended or tested.

      At first, when loading is light, problems may not be extremely obvious. However, as the load increases, voltage distortion and flat-topping will also increase until problems do arise. Although neutral current can be reduced, it is often achieved at the expense of a tremendous increase in voltage distortion. At 30%, the voltage distortion can be up to 4 times the maximum limit of 8% recommended by IEEE std 519. In addition, the measured crest factor can be significantly below the normal sinusoidal crest factor of 1.414.

      4. The 180 Hz L-C blocking filters requires the use of capacitors and it is well known that capacitors are less reliable than inductors and transformers. Failure of the capacitor or its protection could result in a very high impedance ground at the neutral over the full frequency range. This would have a dramatic effect on 60 Hz unbalance and fault currents.

      5. At frequencies above the resonant point (180 Hz), the parallel L-C circuit becomes capacitive which could result in a resonant condition at some higher harmonic frequency.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • Can equipment manufacturers design their products to be free of harmonics

      Category:

      Tags: harmonics

      Yes they can, but lowering the current distortion levels at the input to the SMPS in a computer will add to the cost of the computer. This is not a step that computer manufacturers wish to take because of the continuous and intense cost cutting in the computer industry.

      Actually it is less costly overall to provide a harmonic mitigating transformer to feed several hundred computers than it is to improve the operation of the SMPS in each computer. This is especially true when we consider that the added cost of the improved SMPS will reappear every three years when a new computer system is purchased.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • Why do 3rd harmonic currents overload neutral conductors?

      Category:

      Tags: harmonics

      Sinusoidal currents on the phases of a 3-phase, 4- wire system with linear loads sum to return on the neutral conductor. The 120° phase shift between the sinusoidal load currents causes their vector sum to be quite small. In fact it will be zero if the linear loads are perfectly balanced.

      The instantaneous sum of the currents in the three phases taken at any moment will also be zero if the linear loads are perfectly balanced. If they are not, then there will be a small residual neutral current.

      With linear loads, the neutral conductor can be the same size as the phase conductors because the neutral current will not be larger than the highest phase current. Unfortunately, this is definitely not true for non-linear phase-to-neutral loads.

      120VAC non-linear loads like the SMPS used in computers and in monitors draw current in two distinct pulses per cycle. Because each pulse is narrow (less than 60 degrees), the currents in the second and third phases are zero when the current pulse is occurring in the first phase. Hence no cancellation can occur in the neutral conductor and each pulse of current on a phase becomes a pulse of current on the neutral.

      Even if the phase currents of the SMPS loads are perfectly balanced in RMS amperes, the RMS value of the neutral current can be as much as √3 times the RMS value of the phase current because there are 3 times as many pulses of current in the neutral than in any one phase. If the phase current pulses do overlap because they exceed 60 degrees in width, then there will be some cancellation so that the neutral current will be less than √3 times the phase current. Overlapped or not, because there are 3 times as many pulses in the neutral than in a phase, the predominant component of the neutral current will be the 3rd harmonic (180Hz for a 60Hz system). The linear current completes only 2 cycles in the same time period that the non-linear neutral current completes 6 cycles or 3 times the fundamental.

      Often, in new construction this situation is addressed by simply doubling the neutral conductor ampacity. In existing facilities however, it is most often very difficult and too costly to implement this solution, therefore an alternate method is usually necessary. Question 11 describes how Zero Sequence Harmonic Filters can be used very effectively to reduce 3rd harmonic currents in the neutral conductor.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • Are there standards that can help in addressing harmonics?

      Category:

      Tags: harmonics

      The standard most commonly applied to the control of harmonics in Power Systems is IEEE standard 519 – 2014, ‘IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems‘.

      This standard recommends maximum acceptable limits for both voltage and current harmonics to prevent problems that can result from heavy non-linear loading. The limits for harmonic currents are designed to minimize the amount of voltage distortion these currents would produce in the power system.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What is a Grounded Conductor (Grounding)?

      Category:

      Tags: grounding

      Grounding metal parts to the earth in premises wiring is only useful to provide a path for lightning, shunting high-frequency noise, or reducing static discharge.

  • What is a Center Tap?

      Category:

      Tags: taps

      It is a center point of a two winding transformer or a true tap in the middle winding of a coil. The voltage from the neutral to the center point will equal the voltage from the center point to end of the coil.

      For three phase units, the center tap is often limited to 5% of the total transformer kVA.

  • What is a Bonded Conductor (Bonding)?

      Category:

      Tags: grounding

      Bonding all metal parts together and then to the system winding (typically to the X0 terminal of a transformer) is done to provide a low-impedance path to the source (system) to facilitate the opening of the circuit-protection device to remove dangerous voltage on metal parts. In addition, bonding the system to metal parts (typically to the X0 terminal of a transformer) stabilizes the system voltage to the metal parts and it provides a zero system reference (to the metal parts).

  • What does the term Banked describe?

      Category:

      Tags: delta, Wye

      Two or three, single-phase transformers can be inter-connected to make a three-phase bank. The primary windings of the single-phase transformers can be connected in Delta or Wye. Likewise the secondary windings can be connected in either a Delta or Wye configuration.

      The equivalent capacity of the bank will be equal to three times the nameplate rating of each single-phase transformer. Usually, this type of installation is more expensive than using a single three-phase transformer. Advantages to banked transformers include:

      • For utility applications, the loss of one transformer in a delta configuration creates an open delta configuration using only two transformers. This will continue to supply power albeit at a reduced total kVA rating.
      • Banked transformers can be used to applications where the size or weight of a three phase transformer is too large. An example would be the ability to move a banked transformer in three lighter and smaller sections in a freight elevator.

  • What does radial-feed mean?

      Category:

      Tags: delta, winding, Wye

      A radial-feed transformer has one fully rated connection point per phase including the neutral point if provided on WYE connected transformers.

  • What does loop-feed mean?

      Category:

      Tags: delta, winding, Wye

      A loop-feed transformer has two separate fully rated connection points per phase. This allows the parallel connection of two or more transformers on one circuit.

  • What are transformer wire leads?

      Category:

      Tags: isolation

      Some transformers, often smaller control or potted units, will use wire leads for their primary and secondary connections instead of copper pads or terminal blocks. Typically these are insulated multistrand wires which are connected to the rest of the circuit using a terminal block, lugs or wire nuts.

  • What are Primary Voltage Taps?

      Category:

      Tags: taps

      In some cases, the actual supply voltage to the primary of the transformer is either slightly higher or lower than the nameplate rating. Taps are provided on most transformers on the primary winding to correct this condition and maintain full rated output voltage and capacity. Standard taps are usually in 2 1/2% or 5% increments.

      Example: The transformer has a 480V primary rating and the incoming voltage is at 504V. The primary connection should be made at the +5% tap in order to maintain the nominal secondary voltage.

  • When can you Reverse Connect a transformer?

      In general, distribution transformers can be reverse connected without de-rating the nameplates KVA capacity. However, this is rarely considered in modern applications due to NEC code changes. Several precautions need to be taken for reverse connection of some smaller transformers. These would include:
      Dealing with higher current inrush which can cause nuisance tripping.

      HPS transformers under 6kVA three-phase and 3kVA single-phase, there is a “turns ratio compensation” on the low voltage winding. When backfed the turns compensation actually reduces the output voltage. When a three-phase transformer is reverse connected thus resulting in a Wye-Delta configuration, the neutral terminal must be isolated. This modification may violate the warranty and agency listings such as U.L.

      Back-fed transformers increase the installer’s liability since a future user may not realize what is the primary while de-energizing the transformer.

      In general HPS suggest that a proper step up transformer which is designed with the low voltage terminals as the primary terminal be used.

  • Can a transformer convert single-phase power to three-phase power?

      Single-phase power can be derived from a three-phase source. Transformers cannot convert a single-phase source to a three-phase source. The typical method to convert single-phase power to three-phase power is to utilize devices generally termed as rotary or static phase converters.

  • What does the dot mean on a single phase transformer wiring schematic?

      Category:

      Tags: single phase, winding

      Typically, a single phase transformer wiring schematic has a dot on both the primary and secondary windings.

      The placement of these dots next to the ends of the primary and secondary windings informs us that the instantaneous voltage polarity seen across the primary winding will be the same across the secondary winding. In other words, the phase shift from primary to secondary will be zero degrees, which is important for some types of circuits. If the wiring to the dots is reversed on one side, the primary and secondary will be 180 degrees out of phase.

  • Explain Balance Loading on Single and Three Phase Transformers?

      A single-phase transformer with a series/parallel 120/240V secondary winding has two separate 120V secondary windings and is usually connected into a 3-wire system. When the winders are wired in series for 240 VAC, 120 VAC can be obtained at either between the neutral and centerpoint or between the centerpoint and 240VAC. If both 240 VAC and 120 VAC are going to be used, care must be exercised in distributing the load on the two 120V windings evenly, so each winding is carrying about half of the total 120VAC load if the 120 VAC load exceeds 5% of the total tranformer rating.

      Similarly for a three-phase transformer, each phase should be considered as a single-phase transformer. When distributing single-phase loads between the three phases, each of the three windings should be evenly loaded with single phase loads.

      Failure to balance loads can cause secondary voltage imbalances, additional transformer losses and high neutral currents. Significantly unbalanced loads can reduce the life of a transformer.

  • What is a Delta connection?

      Category:

      Tags: delta

      The delta connection is a standard three phase connection with the ends of each phase winding connected in series to form a closed loop with each phase 120 degrees from the other.

  • Describe a Flexible Connection.

      Category:

      Tags: sound level, vibration

      A flexible conduit connection is used to mitigate the transfer of noise and vibration through the conduit.

      A flexible conductor connection is used to connect rigid bus duct between the transformer and switchgear.

  • Can variable frequency drives be powered from an open delta system?

      Category:

      Tags: performance

      There are several issues that occur when a Variable Frequency Drive (VFD) is powered from an open delta system:

      • Uneven voltages in an open delta circuit can cause the diode bridge to unevenly draw current which causes additional heating.
      • The current harmonic distortion caused by the diode bridge will also not be balanced line to line which will cause even more additional heating.
      • Some utilities may require a harmonic study to be performed anytime a large VFD load is to be supplied by an open delta system.

      Overall, an open delta system can result in shorted diodes or DC bus capacitor failures on a VFD. Using DC Link Chokes and/or Line Reactors will mitigate some of this additional distortion. The VFD may need to be de-rated for open-delta configurations.

  • What is Parallel Operation?

      Single and three phase transformers may be operated in parallel by connecting similarly marked terminals, provided their ratios, voltages, resistances, reactance and ground connections are designed to permit parallel operation. Current and voltage angular displacements are also required to be the same in the case of three phase transformers.

  • What is a Zig-Zag Connection?

      Category:

      Tags: grounding

      It is a special transformer connection commonly used in grounded transformers or harmonic mitigating transformers.

  • What is a Tap?

      Category:

      Tags: taps

      A tap is a connection brought out of a winding at some point between its extremities, usually to permit changing the voltage or current ratio.

  • What is a Scott T Connection?

      Category:

      Tags: single phase

      It is a connection for poly-phase using two special single-phase transformers. Usually used to change from two-phase to three-phase or three-phase to two-phase.

  • What is a Short Circuit?

      Category:

      Tags: FAQ

      A short circuit condition occurs when an abnormal connection or relatively low impedance occurs between to points of different potential in a circuit

  • Under what circumstance is D.C. Resistance Measurement needed?

      Category:

      Tags: tests

      Current from a D.C. resistance bridge is applied to the transformers windings to determine the D.C. resistance voltage of the coils. This test is important for the calculation of transformer winding heat losses used for winding temperature testing, and as base data for future assessment in the field.

  • What is a Full Capacity Tap?

      Category:

      Tags: taps

      A full capacity tap is one through which the transformer can deliver its rated kVA output without exceeding the specified temperature rise.

      Transformers may be designed with full capacity taps ABOVE or BELOW nominal (FCAN and FCBN, respectively). Full capacity taps allow for the input primary voltage to be increased or decreased from its nominal voltage while retaining its ability to deliver its rated kVA output without exceeding it’s specified temperature rise.

  • What is the base temperature rise of a transformer?

      Category:

      Tags: temperature

      The base temperature rise of a transformer is the maximum temperature rise at the expected full load capacity. Transformers can be built to run cooler than the base temperature rise, these are typically referred to as lower temperature rise transformers which can either operate in higher ambient temperatures or have additional service factor.

      • 105C Insulation System: 55C Base Temperature Rise
      • 150C Insulation System: 80C Base Temperature Rise
      • 180C Insulation System: 115C Base Temperature Rise
      • 220C Insulation System: 150C Base Temperature Rise

      The Hot Spot Allowance is added the expected ambient temperature and full load temperature rise to get the total expected temperature rise of a transformer.

  • Buck-Boost transformers are almost always installed as autotransformers. Does the National Electrical Code (NEC) permit the use of autotransformers?

      Category:

      Tags: Buck-Boost

      Autotransformers are very common and recognized by all the safety and standard authorities.

      You can refer to N.E.C. Article 450-4, “Autotransformers 600 Volts, Nominal, or Less”, as a reference publication. Item (a) details over-current protection for an autotransformer, and Item (b) covers an isolation transformer being field connected as an autotransformer for a Buck-Boost application.

  • What is preferred for a neutral grounding transformer?

      Category:

      Tags: Wye

      It is up to the user to specify this. Typically, The most common magnetic grounding device is a zig-zag autotransformer. This design offers greater flexibility at a cost and size smaller than a comparable Wye-Delta isolation transformer.

  • How do I use a Grounding Transformer?

      Category:

      Tags: grounding

      Three-phase grounding transformers provide an artificial neutral for grounding. The main requirement is a specific zero-sequence impedance from the Zig-Zag or the Wye/Delta transformer in addition to the fault current withstand rating. For grounding purpose, only the Zig-Zag or a Wye/Delta connected transformer can be used. Autotransformers will have a high zero-sequence impedance and hence, cannot be used for grounding. Air-core reactors can be normally connected between the artificial neutral and ground to provide some additional current-limiting impedance.

      Grounding transformers are often required by the utility to attach a load generator such as solar, wind or a generator to the power grid.

  • Why is the isolation transformer kVA rating shown on the nameplate instead of the autotransformer kVA rating?

      Category:

      Tags: isolation

      Shipped as an isolating transformer, the nameplate is required to show the performance characteristics accordingly. Additionally, as an autotransformer, the eight different combinations of voltages and kava’s would be impractical to list on the nameplate. A connection chart, listing the various connections, is included with each unit.

  • Do I need to connect the neutral and ground my HPS three-phase autotransformer?

      Category:

      Tags: grounding

      If the application needs a neutral (including 3 phase 4 wire systems), the autotransformer must be ordered with the optional neutral terminals (“3L0U” suffix).

      This option will provide the customer with a common (H0/X0) neutral connection point that is connected by the factory to the middle point of the Y winding configuration.

      When selecting this option, both the Line and Load side neutral cables must be connected to the respective neutral terminals in order to ensure the proper operation of the autotransformer.

      HPS does not recommend that the transformer H0/X0 point be grounded locally.

      When an autotransformer without neutral connections is selected, typically the neutral is grounded at the source transformer secondary and is properly referenced throughout the whole installation and carried through to the end load downstream the autotransformer.

      When installing an autotransformer with neutral connections problems can occur when the X0 point of the autotransformer is grounded locally. In such cases a multiple grounding situation may occur which would be against the electrical codes in North America.

      In the above case typically the upstream transformer secondary is grounded at the X0 point of the Y secondary (GND1), in the meantime grounding the X0 point of the autotransformer would create a secondary ground (GND2). Since the two grounds are typically in two different locations, likely far away from each other they will be at different ground potentials.

      This situation can create a number of issues including:

      With the two grounds at different potentials, if the autotransformer center point (X0) is used as a neutral, the line voltages compared to that local neutral would be unbalanced. The extent of the unbalance would depend on the extent of the potential difference between the two grounds (GND1 and GND2). This unbalance could cause issues with the equipment connected to the autotransformer.

      Grounding the X0 of the autotransformer will force the center point of the Y to be always at a certain potential, defined by the local ground. However the voltages of the lines coming into the autotransformer are referenced to the ground point of the upstream transformer. The likely scenario is that the two grounds will be at different potentials which will result in conflicting reference points at the autotransformer. The autotransformer and the electrical system will try to resolve the conflict and equalize the two ground points. The only way that can happen is by having ground current flowing between the two grounds.  Depending on how much of a difference in voltage potential there is between the two grounds and also depending on the ground resistances, there can be a significant current flow through the wye center points.  Adding to this fact that the impedance of an autotransformer is typically low, there could be enough current through the autotransformer to burn out one or more coils of the autotransformer.

      The effects and resulting problems that occur due to improper grounding can be unpredictable and manifest themselves differently in time. Ground potentials can greatly vary depending on environmental conditions.  After installing an autotransformer and grounding the center point of the wye (X0) problems may not surface initially.  However, there is a chance that after a rainstorm or some other event, all of a sudden the user experiences high ground currents just because the grounding conditions have changed.  These problems could be very intermittent in nature and hard to diagnose.

      When an autotransformer with neutral connections is requested, we do not recommend the grounding of the X0 point and recommend that the customer and installing contractor should refer to the local electrical code requirements for grounding and the short circuit protection of a three phase autotransformer.

  • What are Motor Starting Autotransformers?

      Category:

      Tags: motor, motor starting

      Motors have a large inrush current upon energization that can stress the electrical system and cause low voltage conditions. Motor Starting Autotransformers (MSAT’s) are used in reduced voltage starters to temporarily reduce the voltage being applied to the motor. This will extend the time it takes the motor to reach full speed and reducing the overall startup current to the motor.

  • How does a buck-boost transformer differ from an isolating transformer?

      Category:

      Tags: isolation

      A Buck-Boost transformer is manufactured as an isolating transformer, with separate primary and secondary windings and is shipped from the factory in that configuration. When field connected for a buck-boost application, the primary and secondary windings are wired together which changes the transformer’s electrical characteristics to those of an autotransformer. The primary and secondary windings are no longer isolated as they are connected together.

  • Can Buck-Boost transformers be used to power low voltage circuits?

      Category:

      Tags: isolation

      Installed as two-winding, isolation transformers, these units can be used to power low voltage circuits including control, lighting circuits, or other low voltage applications that require 12, 16, 24, 32 or 48 volts output, consistent with the secondary of these designs. The unit is connected as an isolating transformer and the nameplate kVA rating is the transformer’s capacity.

  • Can Buck-Boost transformers be used on 3 phase systems?

      Category:

      Tags: three phase, Wye

      Interconnecting two or three single-phase units will readily accommodate three phase systems. The number of units to be used in a 3-phase installation depends on the number of wires in the supply line. If the 3-phase supply is 4-wire Wye, then three Buck-Boost transformers are required. If the 3-phase supply is 3-wire Wye (neutral not available), two Buck-Boost transformers are needed.

      Refer to the Corresponding Three-Phase Section in Catalogue

  • Should Buck-Boost transformers be used to develop 3-phase 4 wire Wye circuits from 3-phase 3 wire Delta circuits?

      No – a three-phase “Wye” buck-boost transformer connection should be used only on a 4-wire source of supply. A delta to Wye connection does not provide adequate current capacity to accommodate unbalanced currents fl owing in the neutral wire of the 4-wire circuit.

  • How does the sound level differ between Buck-Boost and isolation transformers?

      Category:

      Tags: isolation, sound level

      Buck-Boost transformers, connected as autotransformers, will be quieter than an equivalent isolation transformer that is rated for the same load. The isolation transformer would have to be physically larger than the buck-boost transformer, and smaller transformers are quieter than larger ones. For example, a 10kVA is 35dB and a 75kVA is 50dB.

  • What is a Buck Boost transformer?

      It is a two-winding, single-phase transformer with low voltage secondary windings, which can be connected as an autotransformer. Used to raise or lower single and three phase line voltages by 10 – 20%.

  • Why do Buck-Boost transformers have 4 windings?

      Category:

      Tags: winding

      A four winding buck-boost transformer with 2 primary and 2 secondary windings can be connected eight different ways to provide a multitude of voltages and kVA’s. This provides the flexibility necessary for the broad variety of applications. A two-winding transformer can only be connected in two different ways.

  • Why are Buck-Boost transformers shipped from the factory connected as isolating transformers, and not pre-connected autotransformers?

      Category:

      Tags: isolation

      The same 4-winding Buck-Boost transformer can be connected eight different ways to provide a multitude of voltage combinations. The user when assessing the supply voltage at site can best determine the correct connection.

  • Why isn’t a ‘closed Delta’ Buck-Boost connection recommended?

      Category:

      Tags: Wye

      This connection requires more kVA power than a “Wye” or open delta connection, and phase shifting occurs on the output. The closed delta connection is more expensive and electrically inferior to other three-phase connections.

  • Transformer is overheating

      Category:

      Tags: FAQ

      Transformer insulation is generally rated for 220°C but may be lower for some designs including control or encapsulated. Standards permit the temperature of the transformer enclosure cover to be 65°C over ambient. When temperatures exceed the rating for the insulation system or enclosure, overheating occurs.

      Burned, darkened or damaged insulation may be apparent along with a burnt smell. The hottest part of a transformer is the coil near the top of the core. Energized transformers should not be touched. If the insulation is damaged or smoke is visible, the unit may need to be returned for testing and replaced or repaired.

      Check: Solution:
      Verify total load doesn’t exceed transformer kVA rating. Reduce size or load or replace with larger transformer. In some cases fans can be added to increase cooling and
      maximum load.
      Verify ambient temperature does not exceed transformer ratings. Relocate to area with lower ambient temperature, reduce load, reduce ambient temperature at primary location or
      replace with a low temperature rise transformer. Transformers installed in small rooms will need proper room
      ventilation.
      Verify tap connections are set up identically on all coils.
      Verify transformer is correctly rated for harmonic load, check for high neutral currents. Reduce or remove harmonic loads or replace transformer with a larger unit or unit with the proper k-rating.
      Verify that the transformer’s ventilation openings are not blocked. Transformers purchased as core and coil
      units and placed in enclosures not supplied by HPS require that the integrator properly size the enclosure and cooling
      requirements.
      Relocate the transformer to an area of better ventilation. Move the transformer away from walls, equipment or
      overhead projections that may impede airflow. Do not install fans to cool a transformer. Improperly installed fans may
      actually impede airflow and could result in transformer damage.
      Improper Input Voltages Verify taps are correctly set for the input voltage. Depending on the load and transformer type, continuous
      overvoltages or undervoltages as low as 5-10% may cause overheating.
      Check no load current. If no load current is high (varies with transformer efficiency but no load current is typically less than 2-3% of
      total kVA), inspect the core and coils for damage. In most cases you will not be able to inspect the insulation between
      the core and coil without returning to the factory for testing and disassembly. If there is a short between the core
      and coil, the unit will have to be replaced or repaired.
      Excessive and sustained airflow caused by exterior winds or fans generally moving horizontally to the ground can
      disrupt convection cooling and cause overheating at high loads.
      Relocate the transformer to an area with less wind or block the wind.
      Fan cooled transformers have broken or misaligned fans. Fans need to be replaced or realigned.
      Low Power Factor Low power factor can cause excessive current and higher overall loads. Current meters need to be able to register
      total current. Some digital meters may not be accurate.
      Unbalanced loads may cause excessive heating. Loads should be balanced to within 20 % of maximum kVA. No individual load should exceed the load specific load for
      each phase (1/3 of total kVA for three phase units).
      Transformer is installed above a heat source such as another transformer. Move either the transformer or the heat source. Redirect the hot airflow from the lower object away from the
      cooling entrances and surfaces of the higher object. Replace the top unit with a low temperature rise transformer.
      Check if output voltage is distorted. A highly distorted output voltage may be a sign that there is a turns to turns fault and the transformer is in
      danged of immediate failure. The transformer needs to be denergized and meggered. The damaged coil may need to be
      replaced or the transformer scrapped.
      Check the output circuits to make sure each leg of the transformer is functioning and overcurrent protection is
      ok.
      If a fuse on one or more of the legs has opened, determine and clear the fault and replace the fuse. This is more
      commong on delta transformer outputs, especially if three single phase units are used in a Delta bank.
      If a Drive Isolation Tranformer (DIT) is being used, verify the DIT kVA has been derated per the HP sizing charts in the catalog. If motor HP is unknown, use .746 kW/HP to determine the equivalent HP of the load. DIT’s are not current rated
      devices, the HP selection charts must be used to properly size a DIT. Extrusion applications tend to be the worst.
      Check if two or more transformers are operating in parallel to power one load. Transformers operating in parallel are rare. Large circulating currents and uneven load can result from
      transformers wired in parallel. The transformer s may have to replaced with one unit capable of power the entire
      load.
      Cable connections are discolored by heating. Cables should be periodically tightened. The surface should be cleaned of any insulation applied during the vacuum
      pressure impregnation process. Rough edges must be smoothed.
      Sparks or smoke is visible from the base of the transformer but the transformer has not failed and there isn’t any sound of arcing. During the VPI process, icicles of insulation can form under the tarnsformer and occassionally act as a ground. If
      discovered early enough the icicle can be removed and the transformer will not be damaged.
      Excessive dust could block air vents Dust needs to be blown out while transformer is denergized.
      Discolored Insulation The transformer’s insulation may have been damaged and may need to be repaired or replaced.
      Visible Flames or Smoke The transformer’s insulation may have been damaged and may need to be repaired or replaced.

  • Corrosion Damage

      Category:

      Tags: FAQ

      Corrosion can damaged the transformers enclosure, core and coils. This can be a consistent problem in corrosive areas such as marine and waste water treatment.

      Check: Solution:
      Check for enclosure and mounting hardware corrosion. Replace corroded parts. In some cases they may need to be replaced with stainless steel or other types of protected parts. Enclosures can be ordered in various grades of stainless steel or with plated base mounting brackets.
      Core steel is corroded. In some cases, light corrosion may not severely damage the core function although a more pressing concern may be conductive rust settling on the coils and causing dielectric problems. In severe cases the core may need to be replaced. Epoxy can be applied at the factory to protect the core from corrosion. Transformers that overheat and damage the insulation are more susceptible to corrosion.
      Coil and conductor corrosion. Protectants such as No-LOX grease may be applied to exposed parts. Only remove insulation from the taps that need to be used. Keep all connections tight. Utilize copper coils when possible. Epoxy coatings (VPE) or encapsulated (potted) transformers can be used.

  • Excessive Conductor Heating

      Category:

      Tags: FAQ

      Cabling attached to the transformer can have excessive heating that causes conductor damage.

      Check: Solution:
      Check conductor connections to make sure they are. Tighten conductor connections. Replace conductors if they are damaged.
      Verify conductors are properly sized. Replace conductors if they need to be sized larger.
      Check conductor insulation rating to make sure it can withstand the high tempertures within the enclosure. Replace with cabling with higher ambient rated conductors.
      Verify conductors aren’t placed above the coils where the warmest air will rise. Reposition conductors in enclosure to avoid the hottest air existing from the top of the coils.

  • Onsite Staff do not know electrical codes or common electrical terms

      Category:

      Tags: FAQ

      HPS greatly appreciates your use of our magnetics in your applications. Our products are meant to be installed by qualified electricians familiar with the local electric codes and the overall system requirements. HPS is the leader in the design and manufacturing of transformers and other magnetics. We are not experts on electrical codes which can vary across the US. Our units are fully compatible with the common installation requirements of the NEC and other local codes. Due to the complexity of electrical systems, there are many questions and problems which require a broad systems solution and local knowledge of the system that we can not offer. Installation by unqualified people can cause equipment failures and dangerous situations.

      Transformer insulation is generally rated for 220°C but may be lower for some designs including control or encapsulated. Standards permit the temperature of the transformer enclosure cover to be 65°C over ambient. When temperatures exceed the rating for the insulation system or enclosure, overheating occurs.

      Burned, darkened or damaged insulation may be apparent along with a burnt smell. The hottest part of a transformer is the coil near the top of the core. Energized transformers should not be touched. If the insulation is damaged or smoke is visible, the unit may need to be returned for testing and replaced or repaired.

  • High Neutral Currents

      Category:

      Tags: FAQ

      High neutral currents can be caused by unbalanced and/or non-linear loads with high harmonics. K-rated transformers have a 200% rated neutral. Amperage should be measured with a meter capable of measuring true RMS currents.

      Check: Solution:
      Check the load to make sure it is balanced. Any load unbalance results in neutral currents. Improve the load balance between the three phases. General purpose transformers have a 125% rated neutral.
      Check the load to determine if it has high amounts of harmonics from single phase sources. For non-linear loads, use k-rated tranformers with 200% rated neutrals. Select a k-rated transformer with a k-factor suitable for the specific level of harmonics.
      Check to make sure all three legs of the transformer or transformer bank are operating. Check coil continuity and blown fuses or tripped breakers. If a fuse is blown, clear the source of the fault and replace the fuse. If a breaker has tripped, clear the fault, check the settings and turn on the breaker.  If the transformer coil is damaged, the transformer will have to be repaired or replaced.  Please contact HPS Customer Service.

  • Noise & Vibration

      Category:

      Tags: FAQ

      Sound levels for transformers vary from 40 dbA for smaller distribution units to 68 dbA for 3000 kVA power transformers and higher for larger units. All transformers vibrate at 120 Hz because the EMF vibrates the unit due to 60 Hz oscillations. The audible noise is measured at no-load and tested in a low ambient noise environment with walls or reflecting surfaces at least 10’ away from the transformer per NEMA ST-20. When installed in more confining electrical rooms and connected to a load, transformers will exhibit higher sound levels than these standards. Transformers can be ordered that produce less noise that the NEMA ST-20 standard, generally at -3 and -5 dB but lower levels are also available. Rubber pads or springs can also be installed between the enclosure and floor to further reduce vibrations and noise. Harmonics generally don’t increase noise too much.

      Check: Solution:
      High Input Voltage Verify taps are correctly set for the input voltage.
      High Frequency If power is coming from a local generator, adjust the generator. If the frequency can’t be adjusted, the transformer may have to be rebuilt.
      Unbalanced Loads Loads should be balanced to within 20 % of maximum kVA. No individual load should exceed the load specific load for each phase (1/3 of total kVA for three phase units).
      Damaged Core. Check any core welds or clamped brackets when fully denergized to make sure the welds are intact and the brackets haven’t slipped. Loose brackets can be tightened on-site but broken welds or cores that have shifted will need to be sent back to the factory for repair.
      Missing Core to Enclosure anti-vibration pads. All ventilated transformers should have rubber pads between the core and enclosure or mounting points. If these are missing they can either be field replaced or the unit can be sent back to the factory.
      Loose Enclosure Tighten enclosure screws and bolts were necessary.
      Transformer mounted on a suspended floor or wall may create and echo chamber and increase noise. Reinforce the floor/wall or move the transformer to a more solid mounting area.
      Multiple transformers installedin one room. Multiple transformers in one area can sometimes resonate with each other and increase the overall noise. The transformers either have to be moved further apart or isolation pads or springs can be mounted under the transformer enclosure.
      Transformer is running correctly but still producing too much ambient noise. A low audible dB transformer can be used to replace the existing unit and/or vibration isolation pads and springs can be installed between the transformer base and floor.

  • No Secondary Voltage

      Category:

      Tags: FAQ

      Transformer secondary voltage can be too high, too low or there may be no voltage. Please note that transformer voltage is a ratio of the primary voltage. If the primary voltage is too high or too low, the secondary voltage will also be too high or too low.

      Check: Solution:
      No secondary voltage. Verify the transformer primary is energized.
      Perform a continuity check on the primary and secondary coils. If a continuity check fails on the secondary, also perform a continuity check on the tap cables. If the tap cables are bad, replace the tap cables. If the continuity check fails and it is not the result of the tap cables, the transformer will need to be either repaired or replaced.
      If one phase a delta secondary has no voltage check to make sure that one of the three legs are grounded. If two legs are grounded, remove the ground from one of the legs.
      Verify all connection points (lugs and pads) are tight, smooth and cleaned of any insulation. Replace jumpers or lugs if they are damaged. Verify the mounting surfaces are clean of insulation and smooth. Verify any mechanical components are tight. In some cases a braise joint at a lug or pad point may be damaged and cause excessive heat.
      Inspect transformer for visual signs of a short circuit including damaged or burned insulation or smoke. If the transformer has been damaged, the transformer may need to be either repaired or replaced.
      Verify all connection points (lugs and pads) are tight, smooth and cleaned of any insulation. Smooth or replace pads and lugs if damaged or rough. Tighten any loose mechanical connections. Clean off any insulation remaining on electrical connection points.

  • Secondary Voltage is Too High

      Category:

      Tags: FAQ

      Transformer secondary voltage can be too high, too low or there may be no voltage. Please note that transformer voltage is a ratio of the primary voltage. If the primary voltage is too high or too low, the secondary voltage will also be too high or too low.

      Check: Solution:
      Verify the taps are set up the same or set up incorrectly for the incoming voltage. Set up taps at the same level and for the correct primary voltage.
      The voltage exceeds the ability of the taps to tune the voltage. A different transformer with a larger tap range or higher input voltage may be needed. Adjust the input voltage to be within the range of the transformer taps.
      The transformer is wired correctly per the input voltage. Verify the transformer being installed is the correct voltage for the application. If the nameplate matches the application, the transformer may be incorrectly nameplated.
      Verify the neutral connection is properly wired and grounded per the applicable codes. All three coils should be attached to a common neutral point. If the transformer neutral is damaged, it will have to repaired. Wire and ground the neutral per applicable codes. A coil may have been inverted during manufacturing and would have to be replaced.
      The transformer is wired correctly per the input voltage. The transformer may be wired in reverse.
      Check the power factor. If the power factor is above 1.0 (leading), high voltages will result. This must be corrected at a systems level.
      Verify the coils are look similar and have similar resistance values. The turns ratio may have been incorrectly wound or one or more of the coils may be incorrect in comparison to the other coils.

  • Transformer is Physically Damaged

      Category:

      Tags: FAQ

      Transformers can become physically damaged during installation or shipping.

      Check: Solution:
      Enclosure is damaged but the core and coil is intact. Minor damage can be repaired in the field with spray paint (scratches) or individual enclosure pieces. Enclosure components located in the base or replacing the entire enclosure will require facilities capable of lifting the entire core and coil Units can also be returned to the plant for enclosure repair and full testing. Encapsulated (potted) units that have enclosure damage may not be repairable.
      Jumpers are damaged. Replace jumpers.
      The coil has been damaged with arcing between the coil taps. Voltage spikes such as lightning or utility transients caused voltages to exceed the transformers BIL ratign and caused arcing. If a conductive dust or liquid (water) is present, this may also cause arcing. The transformer will need to be repaired or replaced. Voltage spikes can be mitigated with lightning arrestors or transformers with higher BIL rates.
      The coil has been damaged with arcing and physcical damage beteen the coils (turn to turn). The insulation between the coils has failed. This may be due to age, overheating, overvoltage or damaged insulation. Each of these failure modes will have to be checked and if found to be a problem fixed. The transformer will need to be repaired or replaced.
      The coil has been damaged with arcing and physcical damage between the coil layers or between the coil and shield. The insulation between the coils has failed. This may be due to age, overheating, overvoltage or damaged insulation. Each of these failure modes will have to be checked and if found to be a problem fixed. The transformer will need to be repaired or replaced.
      Connections points show signs of heat including damaged insulation or excessive corrosion. Replace jumpers or lugs if they are damaged. Verify the mounting surfaces are clean of insulation and smooth. Verify any mechanical components are tight. In some cases a braise joint at a lug or pad point may be damaged and cause excessive heat.
      Coil is damaged. Coil damage can include insulation that has been ripped, worn or is burnt or discolored from heat. Some units can beturned to HPS for repair or coil replacement. In some cases it may be more economical to replace the unit than to repair it.

  • Secondary Voltage is Too Low

      Category:

      Tags: FAQ

      Transformer secondary voltage can be too high, too low or there may be no voltage. Please note that transformer voltage is a ratio of the primary voltage. If the primary voltage is too high or too low, the secondary voltage will also be too high or too low.

      Check: Solution:
      Verify the taps are set up the same or set up incorrectly for the incoming voltage. Set up taps at the same level and for the correct primary voltage.
      The voltage exceeds the ability of the taps to tune the voltage. A different transformer with a larger tap range or higher input voltage may be needed. Adjust the input voltage to be within the range of the transformer taps.
      The transformer is wired correctly per the input voltage. Verify the transformer being installed is the correct voltage for the application. If the nameplate matches the application, the transformer may be incorrectly nameplated.
      Verify the neutral connection is properly wired and grounded per the applicable codes. All three coils should be attached to a common neutral point. If the transformer neutral is damaged, it will have to repaired. Wire and ground the neutral per applicable codes. A coil may have been inverted during manufacturing and would have to be replaced.
      The transformer is wired correctly per the input voltage. The transformer may be wired in reverse.
      Check the power factor. If the power factor is above 1.0 (leading), high voltages will result. This must be corrected at a systems level.
      Verify the coils are look similar and have similar resistance values. The turns ratio may have been incorrectly wound or one or more of the coils may be incorrect in comparison to the other coils.

  • Secondary Voltage Varies

      Category:

      Tags: FAQ

      Transformer secondary voltage can be too high, too low or there may be no voltage. Please note that transformer voltage is a ratio of the primary voltage. If the primary voltage is too high or too low, the secondary voltage will also be too high or too low.

      Check: Solution:
      Incoming line voltage varies. A transformer is a voltage ratio device so the secondary voltage will generally vary as the primary voltage varies. This is a systems issue a transformer can not fix.
      Verify all connection points (lugs and pads) are tight, smooth and cleaned of any insulation. Smooth or replace pads and lugs if damaged or rough. Tighten any loose mechanical connections. Clean off any insulation remaining on electrical connection points.
      Verify the neutral connection is properly wired and grounded per the applicable codes. All three coils should be attached to a common neutral point. If the transformer neutral is damaged, it will have to repaired. Wire and ground the neutral per applicable codes. A coil may have been inverted during manufacturing and would have to be replaced.
      Are there any large loads that occur where total standard or momentary inrush load exceeds the kVA rating of the transformer. During high current, such as when a large motor is started across the line or during a short circuit, the output voltage will be lowered. The total load will either have to be decreased, limited by devices such as reduced motor starting devices or a larger transformer will have to be installed.

  • Smoke is visible or smelled

      Category:

      Tags: FAQ

      Smoke normally means the tranformer’s insulation has been damaged or weakened and failure could have already occurred. The transformer must be immediately deenergized to prevent further damage.

      Check: Solution:
      Visible signs of damaged or failed insulation. The transformer will have to be sent back to the factory for testing and possible repair or replacement. In many cases, it may not be economically possible to repair a damaged tranformer and the unit will have to be replaced.
      No visible signs of damage. The transform should be meggered. If the insulation values are lower than required (consult the maintenance manual), the transformer will have to be sent back to the factory for testing and possible repair or replacement. In many cases, it may not be economically possible to repair a damaged transformer and the unit will have to be replaced.
      No visible signs of damage. Check vertical air ducts in the transformer. If any metallic ferrous metal (screws, nuts, washers, etc.) have fallen between the transformer coils, these will heat through eddy currents and cause insulation damage and eventual failure.
      No visible signs of damage. The transform should be meggered. If the insulation values are within the required range and if the transformer was just manufactured (consult the maintenance manual), the transformer may have some insulation that was not cured during the bake cycle. Please call HPS for further instructions.

  • Transformer has been backfed

      Category:

      Tags: FAQ

      HPS does not recommend that transformers be backfed due to safety issues. The nameplate no longer matches the application and may violate electrical codes and common wiring practices. Backfed transformer are susceptible to high inrush currents, voltage unbalances and lower than expected output voltages.

      Check: Solution:
      Inrush current is causing nuisance tripping. Size the fuse or breaker to the largest allowed by the local electrical code and use time delay fuses or high short circuit trip points on breakers. Replace with a step up transformer is problem persists.
      Output voltage is lower than expected. Windings are turns compensated to take into account the natural voltage drop which occurs in the wires. When a transformer is backfed, the voltage drop still occurs but the winding compensation works in reverse. If possible, use taps to adjust. Replace with a step up transformer if the problem persists.
      Is the transformer a delta-wye transformer that is being backfed such that the wye becomes the primary. This application is not suggested and involves the removal of ground straps which would violate the UL listing of the transformer. This must be replaced with a custom step up transformer.

  • Transformer has been stored in humid area or exposed to water

      Category:

      Tags: FAQ

      If a transformer has been stored deenergized in a humid area, the windings and insulation may absorb water decreasing the dielectric strength of the insulation. In worst cases the windings have been exposed directly to water or submerged in it. If a transformer has been exposed to any liquid, immediately denergize and remove from service.

      Check: Solution:
      If the transformer has been stored in a humid area, megger the transformer. If the insulation ratings are lower than needed, consult the factory. Dry hot air may need to be directed over the transformer for 24 hours ore more. In some cases, the transformer may need to be baked in industrial ovens to sufficiently dry out.
      If the transformer coil has been exposed to rain or other dripping water, megger the transformer. Immediately remove from service. Since liquid water can shift, even a proper megger reading may not be sufficient. Consult the factory. Dry hot air may need to be directed over the transformer for 24 hours or more. In some cases, the transformer may need to be baked in industrial ovens to sufficiently dry out.
      If the transformer has been exposed to a liquid other than water, please consult the factory. Some chemicals may leave conductive or corrosive residue that weakens the insulation. In this case, the transformer may need to be repaired or replaced.
      If the transformer coil has been submerged in water, consult the factory. In this case, the transformer will usually need to be replaced or returned to the factory for evaluation and possible repair.

  • Transformer is covered in dust

      Category:

      Tags: FAQ

      During normal operation, transformers can become covered in dust which needs to be periodically cleaned off to prevent arcing and loss of cooling capacity.

      Check: Solution:
      Is dust simple non-conductive dust. Denergize and blow off with compressed air.
      Is dust corrosive such as salt. Simply blowing off the dust may not be sufficient to protect the transformer from corrosion. Megger checks may not diagnose some of these problems. Transformers may need to be placed in a location away from corrosive dust. The transformer may need to be professionally cleaned by manufacturer or replaced. Please consult factory. Certain coatings such as epoxy (VPE) or encapsulated (potted) transformers are available.
      Is dust conductive such as coal, carbon black or metallic. Simply blowing off the dust may not be sufficient to protect the transformer from coronal discharge or short circuiting. Megger checks may not diagnose some of these problems. Transformers may need to be placed in a location away from conductive dust.

  • Nuisance Tripping of Fuses or Breakers at Energization

      Category:

      Tags: FAQ

      When a transformer is energized, it draws a large current for a few cycles to establish the eletromagnetic field. During this time, the transformer load has little to no effect on the initial transformer inrush. Inrush can vary depending on where the sine wave is during initial energization and how long the transformer was denergized before being energized again. Inrush current can be up to 12 times rated FLA current. In some cases custom transformers can be built to have very low inrush values.

      Check: Solution:
      Are overcurrent device sized correctly per applicable codes. Size overcurrent devices correctly. NEC code should be reviewed. In general buck-boost overcurrent protection should be sized NEC 450-4 which is also found in the back of our buck boost section in the catalog. 600 volt class distribution overcurrent protection should be sized per NEC Table 450.3(A).
      Are overcurrent devices time delay? If overcurrent devices are quick trip, replace with time delay version.
      Overcurrent devices are sized for a load which is significantly lower than the rated transformer amperage. Overcurrent devices should be sized for the transformer amperage since inrush is dependent on transformer size and not load.
      Is the transformer being back fed? Backfeeding is generally done when taking a standard step down transformer and using it to step up the voltage which reverses the order of energization for the windings. Transformers being backfed will experience higher inrush currents since the coil being energized (secondary) is further from the core. In this case the overcurrent devices should be sized to the maximum allowed per the applicable code requirements. In some cases a custom transformer may need to be used instead of backfeeding a standard transformer.
      Is the input voltage higher than the input is set up for? Lower the input voltage, adjust the taps or use a transformer capable of adjusting for a higher input voltage.
      Check in the input frequency, lower input frequencies can cause higher inrush currents. Adjust the input frequency or replace transformer with a unit capable of using a lower frequency (us a 50/60 Hz core).
      Check the core to make sure it is properly aligned, tight and has not shifted. If possible tighten any core clamps. If the core has shifted or is damaged, it may have to be repaired or replaced. Bad core steel or a core built too small for the application would have similar problems.
      Check the coil insulation. Shorted turnscan cause nuisance tripping initially but this will quickly turn into a turn to turn fault which will destroy the coil.
      Check the primary power factor. Low power factor can cause higher inrush currents. This is a systems problem that will require power factor correction.

  • Can wire or cable be located above a transformers core and coil?

      Category:

      Tags: enclosure

      HPS recommends side or bottom entry for conduit into a type 3R, 12, 4 and 4X enclosure. Neither U.L. or NEC addresses this specifically with transformers. C.S.A. C22.2 No. 47 does address this and disallowed cable entry from the top of the enclosure. The issue with insulated cables is a transformer cools by convection with air moving from the bottom to the top of the coils. The air exiting from the top of the coils can be heated significantly higher than ambient. Cables which enter through the top of the enclosure will experience this heated air which causes three issues:

      • Cable insulation damage within the enclosure.
      • Hot air entering the conduit can cause insulation damage with the conduit.
      • Hubs must be used to prevent water intrusion

      Because of these issues, HPS does not recommend that cable enter through the top of a transformer’s enclosure in any application. Note that some of these issues can be mitigated if using non-jacketed hard bussing instead of cable.

  • Can conduit be installed through the top of an enclosure?

      Category:

      Tags: enclosure

      HPS recommends side or bottom entry for conduit into a type 3R, 12, 4 and 4X enclosure. Neither U.L. or NEC addresses this specifically with transformers. C.S.A. C22.2 No. 47 does address this and disallowed cable entry from the top of the enclosure. The issue with insulated cables is a transformer cools by convection with air moving from the bottom to the top of the coils. The air exiting from the top of the coils can be heated significantly higher than ambient. Cables which enter through the top of the enclosure will experience this heated air which causes three issues:

      • Cable insulation damage within the enclosure.
      • Hot air entering the conduit can causing insulation damage with the conduit.
      • Hubs must be used to prevent water intrusion

      Because of these issues, HPS does not recommend that cable enter through the top of a transformer’s enclosure in any application. Note that come of these issues can be mitigated if using non-jacketed hard bussing instead of cable.

  • What is the difference in enclosures for indoor and outdoor non-hazardous applications?
  • Are there any transformers exempt from this legislation?

      As defined by DOE 10 CFR 431.192 a Distribution transformer means a transformer that—

      • Has an input voltage of 34.5 kV or less;
      • Has an output voltage of 600 V or less;
      • Is rated for operation at a frequency of 60 Hz; and
      • Has a capacity of 10 kVA to 2500 kVA for liquid-immersed units and 15 kVA to 2500 kVA for dry-type units.

      These are the transformers subjected to the DOE 2016 requirements.

      Exceptions are defined by the same DOE 10 CFR 431.192.(5):

      • The term “distribution transformer” does not include a transformer that is an:
      1. Autotransformer;
      2. Drive (isolation) transformer;
      3. Grounding transformer;
      4. Machine-tool (control) transformer;
      5. Non-ventilated transformer;
      6. Rectifier transformer;
      7. Regulating transformer;
      8. Sealed transformer;
      9. Special-impedance transformer;
      10. Testing transformer;
      11. Transformer with tap range of 20 percent or more;
      12. Uninterruptible power supply transformer; or
      13. Welding transformer.

      Drive (isolation) transformer means a transformer that:

      1. Isolates an electric motor from the line;
      2. Accommodates the added loads of drive-created harmonics; and
      3. Is designed to withstand the additional mechanical stresses resulting from an alternating current adjustable frequency motor drive or a direct current motor drive.

  • What are the types of transformers affected by DOE 2016 and NRCan 2019?
  • Can I still sell my C802.2 efficiency transformers that I have in stock after NRCan 2019?

      Transformers physically located in Canada at a distributor or contractor with a manufacturing date before May 1st, 2019 are allowed to be re-sold and installed in Canada. Manufacturers including HPS will not be able to sell non-NRCan 2019 compliant transformers after May 1st, 2019, manufacture’s existing stock is not grandfathered into the new regulations.

  • What are the Energy Efficiency levels mandated by DOE as of January 1st 2016?

      The US Department of Energy (DOE) has regulated the energy efficiency level of low-voltage (LV) dry-type distribution transformers in US since 2007, and liquid-immersed and medium-voltage (MV) dry-type distribution transformers since 2010.

      DOE’s CFR (Code of Federal Regulation) title 10, part 431 defines the current energy efficiency standards for distribution transformers sold in US also known as TP1 energy efficiency levels as adopted by NEMA. Effective Jan. 1st 2016 DOE’s CFR 10 p.431 will require new higher levels of Energy Efficiency for transformers installed in any US territory as published in the Federal Register Vol. 78, No. 75 on April 18, 2013.

      Any Distribution transformer manufactured on or after Jan. 1st 2016 and sold in any US state will have to comply with the new energy efficiency levels defined by this document.

      Q2: What are the types of transformers affected?

      The three types of distribution transformers covered by the standard are: low-voltage dry-type, liquid-immersed, and medium-voltage dry-type distribution transformers.

      Q3: What are the Energy Efficiency levels mandated by DOE as of January 1st 2016?

      The new Energy Efficiency levels mandated as of Jan.1st 2016 are as follows:

      Amended Energy Conservation Standards for Low-Voltage Dry-Type Distribution Transformers

      Single phase   Three phase  
      kVA Efficiency (%) kVA Efficiency (%)
      15 97.7 15 97.89
      25 98 30 98.23
      37.5 98.2 45 98.4
      50 98.3 75 98.6
      75 98.5 112.5 98.74
      100 98.6 150 98.83
      167 98.7 225 98.94
      250 98.8 300 99.02
      333 98.9 500 99.14
          750 99.23
          1000 99.28
      Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431.

      Bottom of Form

       

       

      Amended Energy Conservation Standards for Medium-Voltage Dry-Type Distribution Transformers

      Single phase       Three phase      
      BIL* kVA 20–45 kV efficiency (%) 46–95 kV efficiency (%) 96 kV efficiency (%) BIL kVA 20–45 kV efficiency (%) 46–95 kV efficiency (%) 96 kV efficiency (%
      15 98.1 97.86 15 97.5 97.18
      25 98.33 98.12 30 97.9 97.63
      37.5 98.49 98.3 45 98.1 97.86
      50 98.6 98.42 75 98.33 98.13
      75 98.73 98.57 98.53 112.5 98.52 98.36
      100 98.82 98.67 98.63 150 98.65 98.51
      167 98.96 98.83 98.8 225 98.82 98.69 98.57
      250 99.07 98.95 98.91 300 98.93 98.81 98.69
      333 99.14 99.03 98.99 500 99.09 98.99 98.89
      500 99.22 99.12 99.09 750 99.21 99.12 99.02
      667 99.27 99.18 99.15 1000 99.28 99.2 99.11
      833 99.31 99.23 99.2 1500 99.37 99.3 99.21
              2000 99.43 99.36 99.28

      Bottom of Form

              2500 99.47 99.41 99.33
      BIL means basic impulse insulation level              
      Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under Appendix A to Subpart K of 10 CFR part 431.

      Bottom of Form

                   

  • What is the energy efficiency regulation compliance in the U.S. and Canada?

      In the past several years, there has been an accelerated rate of change in updating energy efficiency standards for transformers in North America.

      Governments in US and Canada are encouraging users to use higher energy efficiency dry-type transformers, to help reduce carbon dioxide emissions. There is also a long term cost savings in operating higher efficiency transformers translated in lower energy usage, lower cooling cost, etc.

      In U.S.A. the Department of Energy (DOE) has mandated new higher efficiency levels effective Jan. 1st 2016.

      In Canada Natural Resources Canada (NRCan) published SOR/2016-311 which amends the Energy Efficiency Act to align the via amendment 14 the minimum energy efficiency levels for dry type transformers to the ones implemented by DOE in Jan 2016.

      The new NRCan 2019 regulation is going to be enforced across Canada on May 1st, 2019. The Ontario government already adopted these new efficiency levels by publishing the ON Reg.404-12 which in schedule 6 defines the new energy efficiency levels that dry type transformers sold in ON must comply with starting Jan.1st 2018 (Ontario Energy Efficiency Compliance).

      The rest of Canada (including Quebec) is still following the current energy efficiency levels prescribed by CSA C802.2, until the new NRCan regulations come in effect on May 1st 2019.

      To help our valued customers in estimating the cost savings resulting from upgrading their old dry type transformer to the new DOE2016/NRCan2019 efficiency levels, HPS has developed an Energy Savings Calculator available on its website. To find out how HPS can help reduce your energy consumption, click here.

      To visit the Canadian Gazette for more information about the Canadian energy efficiency standards, click here.

      For the Ontario Energy efficiency regulation please click here.

      To view an electronic copy of the U.S. DOE energy efficient standards, click here.

  • Will NEMA Premium transformers continue to be offered?

      NEMA premium represents energy efficiency levels that are higher than TP1/C802.2 efficiencies but lower (or equal on some kVA levels) than DOE 2016 and NRCan 2019 efficieny levels. As a result NEMA Premium transformers were largely removed from the North American market in 2016 and replaced with units which met the DOE 2016 and NRCan 2019 efficiency levels.

  • What are the environmental benefits of this change?

      According to DOE, the new amendments to the existing efficiency standards would further decrease electrical losses by about 8 percent for liquid-immersed transformers, 13 percent for medium-voltage dry-type transformers, and 18 percent for low-voltage dry-type transformers. In addition, about 264.7 million metric tons of carbon dioxide emissions will be avoided, equivalent to the annual greenhouse gas emissions of about 51.75 million automobiles.

      Beginning in 2016, newly amended energy efficiency standards for distribution transformers will save up to $12.9 billion in total costs to consumers — ultimately saving families and businesses money while also reducing energy consumption. The new distribution transformer standards will also save 3.63 quadrillion British thermal units of energy for equipment sold over the 30-year period of 2016 to 2045.

  • What are the new Energy Efficiency levels in place for the Canada in 2019?

      Transformers have been and remain an essential part of our electrical infrastructure. Everywhere we look there is a transformer supplying power to industrial, commercial or residential applications.

      In the past decades the greenhouse gas emissions and the effects on our planet have become the focus of many governments, agencies and individuals. Energy generation is a major contributor to the greenhouse gas emissions. In addition to widespread efforts to make energy generation more environmentally friendly, there is also a goal to lower energy consumption within most industrial, commercial and residential areas. Achieving increased energy efficiency levels for equipment and consumer products has become a priority for many manufacturers.

      Improving the energy efficiency of new transformers is a primary goal of the Department of Natural Resources (French: Ministère des Ressources naturelles), operating under the FIP applied title Natural Resources Canada (NRCan). It has the legal authority to define efficiency levels and enforce compliance. Environmentally conscious consumers also recognize that buying a higher energy efficiency transformer will have a societal payback over many years.

      NRCan has established new and more stringent Energy Efficiency levels for Transformers in Canada effective May 1st, 2019 that is generically referred to as NRCan 2019. The new efficiency levels for Medium Voltage Liquid-Filled, Medium Voltage and Low Voltage Dry-Type Distribution Transformers are defined byNRCan and largely follow the U.S.A.’s efficiency leves in the DOE’s 2016 CFR (Code of Federal Regulations) title 10 part 431. The new efficiency levels are expected to reduce energy losses by an average of 18% in low-voltage dry-type distribution transformers and 13% for medium-voltage dry-type transformers, over the current C802.2 efficiency levels.

      To put the benefits of this change in perspective, the U.S.A’s DOE projects savings up to $12.9 billion (U.S.) in total costs to consumers and 3.63 quadrillion Btu of energy over a 30 year period. In addition, about 265 million metric tons of carbon dioxide emissions will be avoided, equivalent to the annual greenhouse gas emissions of about 52 million automobiles. Canada can expect similar benefits but scaled to Canada’s overall economy.

      The subject of energy efficiency for transformers raises two main considerations:

      (1) Under normal operation a transformer is always on (typically at 35% average loading), making any energy efficiency improvements more significant over an extended period of time. This means that customers will be rewarded in two manners: they are reducing greenhouse gas emissions and there is an economic payback through reduced energy costs.? Considering the life expectancy of a transformer and the fact that the transformer will be on 24 hours a day, 7 days a week for the next 25-30 years, even small energy efficiency improvements will pay dividends for decades.? A secondary benefit is that more efficient transformers generate less heat, and in many cases this translates into lower costs to cool the environment in which they are utilized.

      (2) The currently mandated energy efficiency levels are already hovering around the 98-99% mark, depending on the type of transformer and ratings. This means that any further efficiency improvements become more challenging to achieve, typically requiring more and/or better core and conductor materials.? This will directly impact the cost of the transformer in most cases. However, as noted in point 1 above, there is an economic benefit to offset the higher initial transformer costs. The new NRCan 2019 compliant transformers that will come on the market will also be somewhat heavier than the current C802.2 efficiency level transformers.

      Hammond Power Solutions (HPS) has an online Energy Savings Calculator to help to our customers determine the savings they can achieve by installing a higher efficiency transformer.? It includes a comparison of transformers with older efficiencies to those of higher efficiency (NRCan 2019 and DOE 2016) as well as specifics of the application and the customer’s cost of energy.

      The Electricity savings resulting from upgrading one three phase 75 kVA transformer can be translated into one of the following:

      • 1.19 Metric Tons of CO2
      • 121 Gallons of Gasoline
      • About 1/6th of the energy used by an average household annually
      • Planting 28 Trees
      • 0.9 Acres of Forest
      • Recycling 0.34 Metric Tons of Waste
      • Savings of $166 per year at $0.12 per kW-Hr

      Dense Forest

      At some kVA ratings NEMA Premium energy efficiency levels meet or slightly exceed the DOE 2016 levels, some are slightly below the new requirements.? However, the NEMA Premium products are optional within the market today, and many consumers do not take advantage of the benefits they afford.? Hence, the DOE will require that all transformers manufactured after January 1st, 2016 will meet the new efficiency levels.

      The environmental impact and savings for our customers resulting from the DOE changes are positive and significant.? HPS fully embraces and supports this change, and the environmental benefits our society will receive as a result.? We proudly offer high quality transformers meeting the most stringent Energy efficiency requirements today and will be in a position to support the migration to the new DOE 2016 higher-efficiency designs for our valued partners and customers, beginning in the latter half of 2015.

      View HPS Transformer Savings Analyzer.

  • Did the DOE 2016 and NRCan 2019 efficiency regulations result in product brand changes for HPS?

      The obsolete HPS TP1/C802.2 rated Sentinel, Synergy, Centurion and Express lines were still available in the Canadian until the NRCan 2019 efficiency levels (same as DOE 2016) were mandated. In addition the older medium voltage Millennium line was still available in Canada until NRCan 2019 May 1st, 2019.

      The older lines were replaced with DOE 2016 and NRCan 2019 compliant low voltage Sentinal G (general purpose), Sentinel K (K rated), Sentinel H (harmonic mitigation) Express G and Tribune E (DIT, Canada only) product lines. In addition the medium voltage Millennium G, Millennium E and EnduraCoil lines also meet the updated DOE 2016 and NRCan 2019 efficiency levels. While exempt from regulations, the Titan N encapsulated transformers often meet or exceed the DOE 2016 and NRCan 2019 regulations.

  • What should I do if I need to quote a project that will ship after NRCan 2019 is implemented?

      To comply with the NRCan 2019 legislation you should quote the new NRCan 2019 efficiency transformers for projects that will ship after May 1st, 2019. However production lead times of a month or more may mean practical orders times April 1st, 2019 or before. To ensure that you accurately capture the specifics and price of the NRCan 2019 products in your quote, please contact our nearest sales office.

  • Can I still sell my TP1 efficiency transformers that I have in stock?

      Transformers physically located in US with a manufacturing date prior to 2016 are legally allowed to be sold and installed in US and its territories after Jan.1st 2016 without any time restrictions. This existing TP1 stock can be sold until depletion before the more expensive DOE2016 product will hit the market.

  • How will the new DOE 2016 and NRCan 2019 compliant Sentinel G, K and H be different from the older TP1/C802.2 lines?

      To achieve the significant decrease in electrical loses mandated by DOE2016 in transformers that are already at 97-99% efficiency, major changes in design and material quality were implemented, resulting in larger cores and overall sizes for the transformers. As a result of these quantitative and qualitative increases, the costs of the new transformers will also increase proportionally.

  • Why is the insulation rating for some distribution transformer set at 220°C and for others the rating is 200°C?

      Category:

      Tags: temperature

      Most standard ventilated distribution transformers use a 220°C insulation system. This insulation system provides a 150°C temperature rise over ambient, a 30°C hot spot and is meant to be installed in a 40°C ambient temperature.

      However, if a transformer is wound using copper wires, a few of the smaller frame sizes (15kVA and 30kVA three phase, 15kVA and 25kVA single phase) utilize a 200°C insulation with a 130°C temperature rise over ambient, a 30°C hot spot and is meant to be installed in a 40°C ambient temperature.

      The differences in these smaller kVA sizes using copper wire are the result of U.L. ratings of the wire’s insulation temperature rating. Copper wire has a significantly smaller diameter than an equivalent ampacity aluminum wire.

      Small copper wire with 220°C insulation is not always available, so insulation systems are limited to 200°C (Note: U.L. does not cover 200°C insulation systems for units greater than 1.2kV, they will use 180°C insulation systems).

      Small control and potted transformers have insulation systems well below 220°C because of the resin used. As a result, transformer manufactures generally rate transformers using copper conductors 30kVA and below as having a 200°C insulation system.

      Manufacturers compensate for this by building the transformers to run cooler at full load and as a result have a lower 130°C temperature rise and can operate in a 40°C environment.

      Because both units can be operated in a 40°C ambient, we say copper transformers 30kVA and below with a 130°C temperature rise are equivalent to larger units with a 150°C temperature rise.

  • What is Dielectric Material in a transformer?

      Category:

      Tags: performance

      The turn-to-turn and layer-to-layer insulating materials of the transformer winding can be referred to as “Dielectric Material”. This typically consists of fiberglass, mica, aramid fiber paper, NOEMX, Mylar, etc.

  • What is the difference between impregnation and encapsulation?

      Impregnation is the complete penetration of the process materials (generically called varnish or epoxy) into the windings of the transformers coils. This is often accomplished by using a Vacuum Pressure Impregnation (VPI) cycle.

      Encapsulation is the complete encasement by the process materials (generically called varnish or epoxy) onto the windings of the transformers coils. In simple terms, the process materials have a thicker, more complete coating than an impregnated transformer. Encapsulation can be done by performing two or more VPI cycles or using a higher viscosity process material. Sometimes “potted” will be used for “encapsulated”.  A Cast Coil transformer would be considered to be both impregnated and encapsulated.

      There is not an industry standard for encapsulation. A winding can be encapsulated, it can be impregnated or it can be encapsulated and impregnated.

  • What is a Dielectric System in a transformer?

      The dielectric system consists of the dielectric materials (fiberglass, mica, aramid fiber paper, NOEMX, Mylar, etc.) in combination with the process materials and air that provides the electrical insulation of the transformer.

  • What are the Advantages and Disadvantages to Using a Fan-Cooled Transformer?

      Advantages:

      • Smaller size; fans may add some height but may reduce width and depth
      • Lower costs for larger units (generally above 1000kVA) to add fans instead of conductor and core
      • Potentially better low-load efficiencies

       

      Disadvantages:

      • Increased complexity and maintenance
      • Increased cost as fan packages may cost more than just adding material in smaller units
      • Additional energy losses and noise when fan motors are operated in higher loads

  • What do I need to specify a neutral grounding transformer?

      Category:

      Tags: impedance

      Neutral grounding transformers are not sized by kVA. To properly specify a grounding transformer, the following parameters must be known:

      1. System Voltage & System BIL
      2. Continuous Neutral Current
      3. Fault Current & Duration
      4. Impedance
      5. Connection Type: Zig-Zag Autotransformer or Wye-Delta
      6. Enclosure Type
      7. Ambient Temperature
      8. Other Environmental Concerns

  • What are Important Specifications for a Marine Duty Transformer?

      Marine Duty is often left to the manufacturer to define.  HPS provides American Bureau of Shipping (ABS) approved transformers which include:

      • Copper or aluminum windings
      • Dry-type convection-cooled
      • Standard NEMA taps
      • 150ºC, 115ºC or 80ºC temperature rise available
      • 220ºC, 200ºC or 180ºC insulation system available
      • VPI Impregnation for salt environments
      • Fungus resistant
      • Braced for marine applications
      • Enclosures:  NEMA 2 or NEMA 3R (per ABS requirements)
      • Stainless steel hardware (on units over 1000kVA)
      • UV protection for outdoor enclosures
      • UL50 frames, channels, etc.
      • CSA, UL and ABS approval (Lloyd’s Register and DNV approval available upon request)

  • What are the types of shielded isolation transformers?

      Category:

      Tags: isolation

      Shielded Isolation Transformers with Single Electrostatic Shield

      This is the simplest type of shielded transformer with one grounded shield extending from top to bottom between the primary and secondary windings. This will typically supply 60dB of common mode noise attenuation from 100Hz through 1MHz. Up to 100dB of TMNA and 40dB at 1000kHz of CMNA can be obtained with effective close coupling and low capacitance.

       

      Shielded Isolation Transformer with Double Electrostatic Shields

      This has two grounded shields extending top to bottom between the primary and secondary windings and between the secondary windings and the core. This will typically supply 60-80dB of common mode noise attenuation from 100Hz through 1MHz.

       

      Shielded Isolation Transformer with Triple Electrostatic Shields

      This has three grounded shields extending top to bottom between the primary and secondary windings and between the secondary windings and core and covering the outer winding. Little benefit is gained by having the third shield. This will typically supply 65-80dB of common mode noise attenuation from 100Hz through 1MHz.

       

      Note that recent testing may indicate that electrostatic shields have little to no benefit in typical applications where the secondary is grounded.

  • How are HPS transformers designed to shield against voltage transients?

      Electrostatically shielded transformers may help minimize or limit the effects of voltage transients. Common Mode noise is measured from line to ground and is usually the most troublesome. Transverse Mode noise is measured from line to line. Attenuation is the difference of an incoming transient on the primary of the transformer to the secondary side.

      An electrostatic or Faraday shield is simply a thin piece of grounded non ferrous metal (generally copper foil) placed between the primary and secondary windings of a transformer. The shield extends from the top to the bottom of the windings. Some manufactures use shields that don’t extend the full length of the coil face. While less expensive, they will not offer as much protection as a full shield.

      There is no national standard that gives test methods for measuring CMNA and TMNA. Hence, in the industry, various companies have different claims that they have succeeded in getting into customer or consultant specifications. A lot of the confusion for shielded transformers results from differing claims made by various manufacturers and experts. Some recent reports indicate that and electrostatic shield may have little to no benefit where the secondary is grounded which is in most applications. The difference in the claims results from many variables:

      1. Standard single shielded distribution and drive isolation transformers may theoretically provide typical values of CMNA =60 dB and TMNA = 10 dB.
      2. A single shielded transformer with a low capacitive coupling of less than 30 pF may theoretically provide typical values of CMNA = 100 dB and TMNA = 40 dB.

      A manufacturer should be willing to share their testing procedures and test circuit to verify their
      claims.

      Note attenuation ratings vary by frequency. As the frequency increases, dB ratings go down. The ratings given above may be best case for a wide range of frequencies from 100Hz to 1MHz. Actual attenuation might be significantly higher at the lower frequencies. Some manufactures may claim higher dB’s attenuation by using much lower frequency ranges.

      There may be a large difference between calculated dB and actual dB due to real-life inconsistencies in material and manufacturing. Manufacturers should have actual test data to back up their attenuation claims.

  • What is the maximum surface temperature of a transformers enclosure?

      Category:

      Tags: enclosure

      Per NEMA ST-20 (2014):

      • Transformers <= 10 kVA can be up to 65C above ambient with a typical maximum ambient of 25C.
      • Transformers > 10 kVA can be up to 50C above ambient with a typical maximum ambient of 40C.
      • Transformers with lower than standard temperature rises will have lower maximum enclosure temperatures.

  • What salt spray rating test have Hammond’s painted enclosures passed?

      HPS enclosures are designed to pass standard U.L. and CSA standards requiring a 600 hour fog test using an atomized 5% salt (NaCl) solution. For applications requiring longer endurance, HPS suggests using 316 stainless steel enclosures.

  • Can transformers be operated above a 1000m/3300′ altitude?

      There are two main considerations for operating transformers at altitudes above 1000m/3300′. Current standards state designs must be valid to these heights. Above this height, the density of air no longer works as effectively to remove heat. As a result the functional kVA of the transformer must be reduced at higher altitudes, typically about .3% for every 100m/330′. The second issue is the dielectric constant of air is reduced at higher altitudes. Dry type transformers use air gaps as an important component of the electrical insulation properties. At higher altitudes, this lower insulation values, typically in medium voltage BIL levels. Ideally, if transformers will be installed above 1000m, inform the manufacturer and the design can be adjusted to meet all requirements at the higher altitudes.

  • What is a Low Voltage General Purpose Transformer?

      Category:

      Tags: low voltage

      HPS’s low voltage general-purpose transformers provide a safe, long lasting, highly reliable power source. They are designed for general lighting and other low voltage applications. They are UL listed and CSA certified.

  • Can I increase the kVA rating of an existing transformer?

      The most common way to increase the available kVA rating of an existing transformer is to add additional fan cooling. This typically requires modifications including raising the transformers core, adding fans and fan brackets, a motor power supply and controls to start fan cooling when the transformer’s components reach a preset temperature. Fans should never be added without contacting and following specific instructions from the manufacturer. Low temperature rise transformers (115C and 80C rise with 220C insulation) can maintain higher loads in lower ambient transformers. Always follow proper ventilation and clearance instructions.

  • Do dry-type, potted or cast resin transformers contain PCB’s?

      Category:

      Tags: cast coil, VPI

      No, dry-type and cast resin transformers do not and have never contained PCB’s.

  • How do you calculate the Total Losses in a transformer?

      Category:

      Tags: loss

      It is the transformer electrical losses, which include no-load losses (core losses) and load losses (winding losses). There is not a specific formula to calculate total losses since they vary by size and manufacturer. Manufacturers will often provide charts that show losses at one or more load points.

      HPS does offer an efficiency calculator for distribution transformers.

      HPS Efficiency Calculator

  • What is the ambient temperature specs for a standard transformer?

      Category:

      Tags: temperature

      A standard transformer with 220°C insulation and a 150°C temperature rise, will be rated to run full load in an average 30°C ambient environment over 24 hours with a maximum 40°C ambient temperature.

      Other magnetics may have lower or higher ambient ratings depending on the design and application.

  • What Seismic ratings Does HPS Use?

      HPS units meet Risk Category IV (Ip=1.5) for Sds=2.0 per ASCE 7-16 (and equivalent factors in NBCC 2015) for ground-level installations only (z/h=0) for all locations in North America.

      HPS units can be designed to meet California OSHPD (Office of Statewide health Planning and Development) requirements. Please see the California OSHPD site for a listing of HPS transformers which have been tested and certified.

  • What is the maximum surface temperature of a transformers terminals wire leads or connections points?

      Category:

      Tags: heat, temperature

      Per NEMA ST-20 (2014):

      • Transformers <= 10 kVA can be up to 50C above ambient with a typical maximum ambient of 25C.
      • Transformers > 10 kVA can be up to 35C above ambient with a typical maximum ambient of 40C.
      • Transformers with lower than standard temperature rises will have lower maximum connection point temperatures.

  • What is the benefit of "Vacuum Pressure Impregnation" on a transformer?

      Category:

      Tags: impregnation

      All HPS transformers and reactors are vacuum impregnated with a “Polyester Resin” and oven cured which seals the surface. Impregnating the entire unit provides a strong mechanical bond and offers protection from environmental conditions.

      Using a vacuum during this process eliminate moisture and provides deeper penetration of insulation into transformer cavities.

  • What is a Control Transformer?

      Category:

      Tags: overload

      A control transformer is an isolation transformer that provides good voltage regulation, and is also designed to provide a high degree of secondary voltage stability (regulation) during a brief period of overload condition (also referred to as “inrush current”). Control transformers are also known as Machine Tool Transformers, Industrial Control Transformers or Control Power Transformers.

  • What Type of Fuses are Recommended for HPS Control Transformers?

      Category:

      Tags: single phase

      HPS recommends the use of time-delay fuses.  The fuse kits offered for the HPS Imperator® product line utilize 13/32″ x 1 1/2″ midget type/CC fuse clips.

  • What are K-Factor Transformers and where are they used?

      Category:

      Tags: harmonics, k-factor

      K-factor transformers are designed to withstand the extra heating and higher neutral currents caused by harmonics created by non-linear loads such as VFD, DC power supplies and LED lighting. K-factor distribution transformers in North America are subject to minimum efficiency regulations in both the U.S.A. and Canada. K-Rated transformers must have:

      • Operate at specific K-rated harmonics without overheating
      • 200% rated neutral
      • Electrostatic Shield

  • What are the new Energy Efficiency levels coming for Transformers sold in the U.S.?

      Transformers have been and remain an essential part of our electrical infrastructure.  Everywhere we look there is a transformer supplying power to industrial, commercial or residential applications.

      In the past decades the greenhouse gas emissions and the effects on our planet have become the focus of many governments, agencies and individuals. Energy generation is a major contributor to the greenhouse gas emissions. In addition to widespread efforts to make energy generation more environmentally friendly, there is also a goal to lower energy consumption within most industrial, commercial and residential areas. Achieving increased energy efficiency levels for equipment and consumer products has become a priority for many manufacturers.

      Improving the energy efficiency of new transformers is a primary goal of the US Department of Energy (DOE), and they have the legal authority to define efficiency levels and enforce compliance.  Environmentally conscious consumers also recognize that buying a higher energy efficiency transformer will have a societal payback over many years.

      The Department of Energy has established new and more stringent Energy Efficiency levels for Transformers in the U.S. effective January 1st 2016.  The new efficiency levels for Medium Voltage Liquid-Filled, Medium Voltage and Low Voltage Dry-Type Distribution Transformers are defined in DOE’s CFR (Code of Federal Regulations) title 10 part 431.  Widely known as DOE 10 CFR p431, it was published in the Federal Register Vol. 78, No. 75 on Thursday April 18, 2013.  According to the DOE, the new efficiency levels are expected to reduce energy losses by an average of 18% in low-voltage dry-type distribution transformers and 13% for medium-voltage dry-type transformers, over the current TP-1 efficiency levels.

      To put the benefits of this change in perspective, the DOE projects savings up to $12.9 billion in total costs to consumers and 3.63 quadrillion Btu of energy over a 30 year period. In addition, about 265 million metric tons of carbon dioxide emissions will be avoided, equivalent to the annual greenhouse gas emissions of about 52 million automobiles.

      The subject of energy efficiency for transformers raises two main considerations:

      1. Under normal operation a transformer is always on (typically at 35% average loading), making any energy efficiency improvements more significant over an extended period of time.  This means that customers will be rewarded in two manners:  they are reducing greenhouse gas emissions and there is an economic payback through reduced energy costs.  Considering the life expectancy of a transformer and the fact that the transformer will be on 24 hours a day, 7 days a week for the next 25-30 years, even small energy efficiency improvements will pay dividends for decades.  A secondary benefit is that more efficient transformers generate less heat, and in many cases this translates into lower costs to cool the environment in which they are utilized.
      2. The currently mandated energy efficiency levels are already hovering around the 98-99% mark, depending on the type of transformer and ratings.  This means that any further efficiency improvements become more challenging to achieve, typically requiring more and/or better core and conductor materials.  This will directly impact the cost of the transformer in most cases.  However, as noted in point 1 above, there is an economic benefit to offset the higher initial transformer costs.  The new DOE 2016 compliant transformers that will come on the market will also be somewhat heavier than the current TP-1 efficiency level transformers.

      Hammond Power Solutions (HPS) has an online Energy Savings Calculator to help to our customers determine the savings they can achieve by installing a higher efficiency transformer.  It includes a comparison of transformers with older efficiencies to those of higher efficiency (TP1, NEMA Premium and DOE 2016 in the future) as well as specifics of the application and the customer’s cost of energy.

      Currently, for applications that require higher energy efficiency than the DOE regulated TP-1 levels, industry is using Premium Efficiency transformers defined by the NEMA Premium Efficiency Guidelines that stipulate approximately 30% lower loses than the TP-1 levels.  In terms of the environmental benefits of using a NEMA Premium transformer over a TP-1 rated let’s look at an example:

      The Electricity savings resulting from upgrading one three phase 75 kVA transformer can be translated into one of the following:

      • 1.19 Metric Tons of CO2
      • 121 Gallons of Gasoline
      • About 1/6th of the energy used by an average household annually
      • Planting 28 Trees
      • 0.9 Acres of Forest
      • Recycling 0.34 Metric Tons of Waste
      • Savings of $166 per year at $0.12 per kW-Hr

      Forest image 

      At some kVA ratings NEMA Premium energy efficiency levels meet or slightly exceed the DOE 2016 levels, some are slightly below the new requirements.  However, the NEMA Premium products are optional within the market today, and many consumers do not take advantage of the benefits they afford.  Hence, the DOE will require that all transformers manufactured after January 1st, 2016 will meet the new efficiency levels.

      The environmental impact and savings for our customers resulting from the DOE changes are positive and significant.  HPS fully embraces and supports this change, and the environmental benefits our society will receive as a result.  We proudly offer high quality transformers meeting the most stringent Energy efficiency requirements today and will be in a position to support the migration to the new DOE 2016 higher-efficiency designs for our valued partners and customers, beginning in the latter half of 2015.

  • Can a transformer be back-fed or used in reverse?

      Category:

      Tags: low voltage, VPI

      In general, distribution transformers can be reverse connected without de-rating the nameplates KVA capacity. However, this is rarely considered in modern applications due to NEC code changes. Several precautions need to be taken for reverse connection of some smaller transformers. These would include:
      Dealing with higher current inrush which can cause nuisance tripping.

      HPS transformers under 6kVA three-phase and 3kVA single-phase, there is a “turns ratio compensation” on the low voltage winding. When backfed the turns compensation actually reduces the output voltage.
      When a three-phase transformer is reverse connected thus resulting in a Wye-Delta configuration, the neutral terminal must be isolated. This modification may violate the warranty and agency listings such as U.L.

      Back-fed transformers increase the installer’s liability since a future user may not realize what is the primary while de-energizing the transformer.

      In general HPS suggest that a proper step up transformer which is designed with the low voltage terminals as the primary terminal be used.

  • New Energy Efficiency levels US 2016

      Transformers have been and remain an essential part of our electrical infrastructure.  Everywhere we look there is a transformer supplying power to industrial, commercial or residential applications.

      In the past decades the greenhouse gas emissions and the effects on our planet have become the focus of many governments, agencies and individuals. Energy generation is a major contributor to the greenhouse gas emissions. In addition to widespread efforts to make energy generation more environmentally friendly, there is also a goal to lower energy consumption within most industrial, commercial and residential areas. Achieving increased energy efficiency levels for equipment and consumer products has become a priority for many manufacturers.

      Improving the energy efficiency of new transformers is a primary goal of the US Department of Energy (DOE), and they have the legal authority to define efficiency levels and enforce compliance.  Environmentally conscious consumers also recognize that buying a higher energy efficiency transformer will have a societal payback over many years.

      The Department of Energy has established new and more stringent Energy Efficiency levels for Transformers in the U.S. effective January 1st 2016.  The new efficiency levels for Medium Voltage Liquid-Filled, Medium Voltage and Low Voltage Dry-Type Distribution Transformers are defined in DOE’s CFR (Code of Federal Regulations) title 10 part 431.  Widely known as DOE 10 CFR p431, it was published in the Federal Register Vol. 78, No. 75 on Thursday April 18, 2013.  According to the DOE, the new efficiency levels are expected to reduce energy losses by an average of 18% in low-voltage dry-type distribution transformers and 13% for medium-voltage dry-type transformers, over the current TP-1 efficiency levels.

      To put the benefits of this change in perspective, the DOE projects savings up to $12.9 billion in total costs to consumers and 3.63 quadrillion Btu of energy over a 30 year period. In addition, about 265 million metric tons of carbon dioxide emissions will be avoided, equivalent to the annual greenhouse gas emissions of about 52 million automobiles.

      The subject of energy efficiency for transformers raises two main considerations:

      (1) Under normal operation a transformer is always on (typically at 35% average loading), making any energy efficiency improvements more significant over an extended period of time.  This means that customers will be rewarded in two manners:  they are reducing greenhouse gas emissions and there is an economic payback through reduced energy costs.  Considering the life expectancy of a transformer and the fact that the transformer will be on 24 hours a day, 7 days a week for the next 25-30 years, even small energy efficiency improvements will pay dividends for decades.  A secondary benefit is that more efficient transformers generate less heat, and in many cases this translates into lower costs to cool the environment in which they are utilized.

      (2) The currently mandated energy efficiency levels are already hovering around the 98-99% mark, depending on the type of transformer and ratings.  This means that any further efficiency improvements become more challenging to achieve, typically requiring more and/or better core and conductor materials.  This will directly impact the cost of the transformer in most cases.  However, as noted in point 1 above, there is an economic benefit to offset the higher initial transformer costs.  The new DOE 2016 compliant transformers that will come on the market will also be somewhat heavier than the current TP-1 efficiency level transformers.

      Hammond Power Solutions (HPS) has an online Energy Savings Calculator to help to our customers determine the savings they can achieve by installing a higher efficiency transformer.  It includes a comparison of transformers with older efficiencies to those of higher efficiency (TP1, NEMA Premium and DOE 2016 in the future) as well as specifics of the application and the customer’s cost of energy.

      Currently, for applications that require higher energy efficiency than the DOE regulated TP-1 levels, industry is using Premium Efficiency transformers defined by the NEMA Premium Efficiency Guidelines that stipulate approximately 30% lower loses than the TP-1 levels.  In terms of the environmental benefits of using a NEMA Premium transformer over a TP-1 rated let’s look at an example:

      The Electricity savings resulting from upgrading one three phase 75 kVA transformer can be translated into one of the following:

      • 1.19 Metric Tons of CO2
      • 121 Gallons of Gasoline
      • About 1/6th of the energy used by an average household annually
      • Planting 28 Trees
      • 0.9 Acres of Forest
      • Recycling 0.34 Metric Tons of Waste
      • Savings of $166 per year at $0.12 per kW-Hr

      Dense Forest

       

      At some kVA ratings NEMA Premium energy efficiency levels meet or slightly exceed the DOE 2016 levels, some are slightly below the new requirements.  However, the NEMA Premium products are optional within the market today, and many consumers do not take advantage of the benefits they afford.  Hence, the DOE will require that all transformers manufactured after January 1st, 2016 will meet the new efficiency levels.

      The environmental impact and savings for our customers resulting from the DOE changes are positive and significant.  HPS fully embraces and supports this change, and the environmental benefits our society will receive as a result.  We proudly offer high quality transformers meeting the most stringent Energy efficiency requirements today and will be in a position to support the migration to the new DOE 2016 higher-efficiency designs for our valued partners and customers, beginning in the latter half of 2015.

  • What is DOE 2016 and how will it affect me?

      The US Department of Energy (DOE) has regulated the energy efficiency level of low-voltage (LV) dry-type distribution transformers in US since 2007, and liquid-immersed and medium-voltage (MV) dry-type distribution transformers since 2010.

      DOE’s CFR (Code of Federal Regulation) title 10, part 431 defines the current energy efficiency standards for distribution transformers sold in US also known as TP1 energy efficiency levels as adopted by NEMA. Effective Jan. 1st 2016 DOE’s CFR 10 p.431 will require new higher levels of Energy Efficiency for transformers installed in any US territory as published in the Federal Register Vol. 78, No. 75 on April 18, 2013.

      Any Distribution transformer manufactured on or after Jan. 1st 2016 and sold in any US state will have to comply with the new energy efficiency levels defined by this document.

  • How can I update my specification to include DOE 2016 compliant product?

      Remove efficiency references to TP1, TP2, TP3, NEMA Premium or CSL (TP1, TP2 and TP3 will be discontinued by NEMA).

      Replace these efficiency requirements with: Efficiency levels must meet the new DOE 10 CFR Part 429 and 431 levels as of January 1st, 2016.

  • What are Electrostically Shielded Transformers and where are they used?

      Electrostatically shielded (Faraday Shield) transformers provides a copper electrostatic shield between the primary and secondary windings. The shield is grounded and thus shunts some noise and transients to the ground path rather than passing them through to the secondary. Transformers having a K-Rating are required to have an electrostatic shield.

      Electrostatically shielded transformers often preferred for electrical installations where electronic circuitry operating at low voltage DC is present and is very sensitive to ‘noise’. Recent testing of electrostatically shielded transformers has questioned their perceived effectiveness where the transformer’s secondary is grounded which would cover most applications.

      Learn more about HPS Sentinel Series

  • Why are the Centurion R® Enclosures so much larger than the Reactor?

      Category:

      Tags: enclosed

      Enclosures must provide enough space for heat dissipation and room for wire bending.

  • Does HPS Have 5% Impedance Centurion® R Reactors at 690 Volts?

      Category:

      Tags: impedance

      Not based on standard motor current ratings. A 5% Z 600 volt reactor will have 4.3% Z impedance at 690 volts. If higher than 4.3% is required, please consult HPS. Often two reactors can be wired in series to provide higher impedance ranges.

      Learn more about HPS Centurion R

  • Can I use the 690 Volt Centurion® R Reactors on the output of my drive?

      Category:

      Tags: FAQ

      690 volt reactors can be placed on the output of a variable frequency drive without de-rating.

  • Are there voltage drop concerns when using a load reactor or dV/dT filter for long lead lengths?

      Yes, there are concerns. Installers should calculate the voltage drop. If the voltage drop falls below the motor’s capabilities, an output drive isolation transformer may be needed instead of or in addition to the load reactors to boost voltage using taps and/or compensated winding ratios.

  • What is the Intended Use of UL Type 3R Enclosures for Centurion R?

      Category:

      Tags: enclosed

      Outdoor applications require an enclosure that provides a degree of protection against falling rain, snow and dirt but are not dust tight.  UL Type 3R enclosures are intended for outdoor use but can also be used indoors.

      Learn more about HPS Centurion R

  • What is the Intended Use of UL Type 1 Enclosures for Centurion® R?

      Category:

      Tags: enclosed

      When your application is indoors, UL Type 1 enclosures provide protection against a limited amount of falling dirt, human protection and vents to provide convection cooling for the unit.

      Learn more about HPS Centurion R

  • When Using a Two or Three Contactor Bypass with a Variable Frequency Drive, Where Should the Input and Output Line Reactors be located?

      The line reactors should be arranged such that the current path for the across the line start contactor does not go through the line reactor.  Line reactors are not designed for motor current inrush present when a motor is energized with an across the line start contactor.

  • How does a HPS Reactor reduce Line Notching?

      Category:

      Tags: line notching

      Whenever a rectifier converts AC power to DC, using a nonlinear device, such as an SCR, the process of commutation occurs. The result is a notch in the voltage waveform. The number of notches is a function of both the number of pulses and the number of SCR’s in the rectifier.

      Reactors are used to provide the inductive reactance needed to reduce notching, which can adversely effect equipment operation.

  • How do HPS Line Reactors handle Heat Dissipation?

      Category:

      Tags: heat

      HPS has designed line reactors with ideal operating features including 50C ambient operating temperature, low temperature rises and reduced losses. HPS reactors will operate efficiently with minimized heat dissipation in your equipment.

      Learn more about HPS Centurion R Reactors

  • How does a Line Reactor minimize harmonic distortion?

      Category:

      Tags: harmonics

      Nonlinear current waveforms contain harmonic distortion. By using a HPS line reactor you can limit the inrush current to the rectifier in your drive. The peak current is reduced, the waveform is rounded and harmonic distortion is minimized. Current distortion typically is reduced to 30%. Severe Harmonic current distortion can also cause the system voltage to distort. Often, high peak harmonic current drawn by the drive, causes “fl at-topping” of the voltage waveform. Adding a reactor controls the current component, and voltage harmonic distortion is therefore reduced.

  • Can a non-inverter duty rated motor be used if load reactor or dV/dT filter is installed?

      Due to wide variations in non-inverter duty rated motors, it can’t be stated that a line reactor or dV/dT filter will fully protect the motor. It’s suggested that as a minimum, a dV/dT filter should be used.

      A full sine save filter may be needed to fully protect non-inverter duty rated motors.

  • What Will the Impedance be at 690 Volts?

      Category:

      Tags: impedance

      The impedance is proportionately lower (600/690 = 86.9%).  690V impedance will decrease from 5.0% to  4.3% or 3.0% to 2.6%.  Current ratings are standard for 600 volt ratings.

      Learn more about HPS Centurion R

  • What is the Impedance of the Centurion® R Reactors?
  • how Line Reactor eliminate Nuisance Tripping

      Category:

      Tags: voltage transients

      Transients due to switching on the utility line and harmonics from the drive system can cause intermittent tripping of circuit breakers. Furthermore, modern switchgear, equipped with solid-state trip sensing devices, is designed to react to peak current rather than RMS current. As switching transients can peak over 1000 volts on a 600 volt system, the resulting over-voltage will cause undesirable interruptions.

      A reactor added to your circuit restricts the surge current by utilizing its inductive characteristics and mitigates nuisance tripping. The impedance of a transformer will have similar effects.

      Learn about HPS Centurion R Reactors

  • Will a HPS Line Reactor extend the life of your motor?

      Category:

      Tags: motor

      Line reactors, when selected for the output of your drive, will enhance the waveform and virtually eliminate failures due to output circuit faults. Subsequently, motor operating temperatures are reduced by 10 to 20 degrees and motor noise is reduced due to the removal of some of the high frequency harmonic currents

  • What Type of Enclosure do I need for my Centurion® R Reactor?

      Category:

      Tags: enclosed

      The enclosure will depend on the degree of protection the reactor must have against indoor and outdoor environments.  Centurion® R Reactors offers Type 1 and Type 3R enclosures.

      Learn more about HPS Centurion R

  • How does a Line Reactor extend the life of switching components?

      Category:

      Tags: FAQ

      Due to the attenuation of line disturbances, the life of your solid state devices are extended when protected by the use of a HPS line reactor.

  • How do the Centurion® R Reactors Have a 600 Volt Rated Insulation System but can be used as a 690 Volt Reactor?
  • Which Centurion® R Reactors are available as UL Listed Products?

      Category:

      Tags: FAQ

      All Centurion® R equal or under 600 Volts are available as a UL Listed product.

  • If an output load reactor or dV/dT filter is installed on a VFD, should VFD Cable be installed from the drive to the motor?

      It is still recommended that users install VFD Cables between the VFD and motor. While a reactor or dV/dT filter can fix some of the issues VFD cable it designed to mitigate, other issues such as low capacitance and EMI/RFI interference can have increased mitigation when VFD cable is used.

  • What are Drive Isolation Transformers and where are they used?

      Category:

      Tags: drive isolation

      Drive Isolation Transformers (DIT) are designed to supply power to AC and DC variable speed drives. The harmonics created by SCR type drives requires careful designing to match the rated hp of each drive system. The duty cycle included is approximately one start every 2 hours. The windings are designed for an over-current of 150% for 60 seconds, or 200% for 30 seconds.

      DIT’s are covered by NRCan efficiency regulations in Canada but are exempt from efficiency regulations in the U.S.A.

  • Does HPS have NRTL certification?

      Category:

      Tags: regulation

      NRTL stands for Nationally Recognized Testing Laboratory. NRTL is used to identify organizations that are qualified to perform safety testing and certification of products covered within OSHA. HPS products carry the UL and CSA marks, so these are considered NRTL certifications.

  • Charging reactor – definition

      An air core reactor that gets used in the motor control circuitry to reduce charging current during switch on.

  • What is a Cast Coil transformer?

      Category:

      Tags: cast coil

      A transformer with coils solidly cast in epoxy resin under vacuum in a mold. Also called cast resin or epoxy cast coil transformers.

  • Capacitor switching reactor – definition

      An air core reactor that is designed to be used with capacitor banks to reduce harmful surge transients during the switching of the capacitor banks on and off.

  • What does the term BIL mean?

      Basic impulse level is a means to express the ability of the insulation system to withstand high voltage surges.

  • What is an Applied Voltage test?

      Category:

      Tags: tests

      A normal power frequency such as 60 Hz is applied to each winding for one minute. These tests are in accordance with table (3) in ANSI C57-12-01.

  • What is ANSI C57.12.91?
  • What does ANSI stand for?

      Category:

      Tags: FAQ

      The American National Standards Institute Inc. – one of the recognized organizations that specify the standards for transformers.

  • What is ANSI C57.12.51?

      IEEE Standard for Ventilated Dry- Type Power Transformers, 501 kVA and Larger, Three-Phase, with High- Voltage 34.5 kV to 601 V and Low- Voltage 208Y/120 V to 4160 V covering General Requirements. The current standard was updated in 2008.

      This standard is intended to set forth characteristics relating to performance, limited electrical and mechanical interchangeability, and safety of the equipment described, and to assist in the proper selection of such equipment. Specific rating combinations are described in the range from 750/1000 to 7500/10 000 kVA inclusive, with high-voltage 601 to 34 500 volts inclusive and low-voltage 208Y/120 to 4160 volts inclusive. Part I of this standard describes certain electrical and mechanical requirements and takes into consideration certain safety features of 60-Hz, two-winding, three-phase, ventilated dry-type transformers with self-cooled ratings 501 kVA and larger, generally used for step-down purposes. Part Il describes other requirements or alternatives which may be specified for some applications and lists forced-air-cooled ratings for certain sizes.

  • What is an air terminal chamber (ATC) or line terminal compartment?

      This is an air filled terminal compartment, typically 12″-24″ wide that is bolted to one or both sides of a substation transformer. This typically contains either the primary or secondary connections with a steel barrier separating it from the larger chamber containing the actual transformer core and coil. The ATC may also contain additional connections for loop feeds and/or lightning arresters.

  • Air core motor starting reactor – definition
  • Will current TP1 Distribution efficiency units be available into Q4/2015 and Q1/2016?

      The supply will be hard to predict.  Many manufacturers will stop production of these units well before January 1st 2016.

      • Supply channel may be hesitant to stock the current TP1 units if specifications are largely updated to support the new regulations.
      • Manufacturers will establish cut-offs for stock replenishment and custom orders 2-5 months before January 1st, 2016.

  • What is a “Dual Winding”?

      Category:

      Tags: winding

      A winding consisting of two separate parts which can be connected in series or parallel. Also referred to as dual voltage or series-multiple winding.

  • What are dust filters?

      Dust filters are placed over ventilation openings to mitigate dust accumulation within the transformer’s enclosure. Filters are typically made to be removable and washable. Care must be taken for regular maintenance since accumulating dust will limit airflow and reduce air cooling. For this reason, dust filters are typically avoided through using non-ventilated designs or moving the transformer’s location. Because of reduced airflow, transformers cannot be retrofitted with dust filters without derating or using fan forced venting.

  • What defines the audible noise levels in a dry type transformer?

      Category:

      Tags: sound level

      NEMA ST-20 (2014) defines the noise level in transformers up to 1.2 kV and up to 1000 kVA.

      NEMA TR-1 defines the sound level for medium voltage transformers above 1.2 kV class up to 7500 kVA.

  • What makes up a Coil?

      Category:

      Tags: winding

      Turns of electrical grade wire or strip conductor material wound on a form, referred to as a winding.

  • What does Dry-Type Self-Cooled Transformer Class AA mean?

      Category:

      Tags: heat, temperature

      A dry-type transformer that is cooled by the natural circulation of air. This is sometimes also referred to as convection cooling.

  • What does Dry-Type Self-Cooled Future-Forced-Air-Cooled Transformer Class AA FFA mean?

      Category:

      Tags: temperature

      Per 1.2.9.4 of NEMA ST-20, a dry-type transformer that has a self-cooled rating with cooling obtained by the natural circulation of air and which contains the provision for the addition of forced-air-cooling equipment at a later date.

  • What does Dry-Type Self-Cooled Force Air-Cooled Transformer Class AA FA mean?

      Category:

      Tags: heat, temperature

      A dry-type transformer that has a self-cooled rating with cooling obtained by the natural circulation of air and a forced-air cooled rating with cooling obtained by the forced circulation of air. This is sometimes referred to as fan-cooled. Fan cooling can increase a transformer’s kVA rating by 25% to 50% depending on the type and size of the transformer.

  • What does Dry-Type Forced-Air-Cooled Transformer Class AFA mean?

      Category:

      Tags: temperature

      Per 1.2.9.3 of NEMA ST-20, a dry-type transformer that derives its cooling by the forced circulation of air.

  • What does DIT stand for?
  • What does Combustible Materials mean?

      Category:

      Tags: heat

      A combustible material is a solid or liquid than can be easily ignited and burned.

  • What does the term “Encapsulated” describe?

      Category:

      Tags: encapsulated

      A transformer with its coils either encased or cast in an epoxy resin or other encapsulating materials. This includes cast coil and potted transformers. Manufacturers may also consider transformers which go through multiple dip and bake cycles creating a thicker coating as encapsulated.

  • What are Distributed Static VAR and Synchronous Compensators (D-SVCs/D-STATCOMs)?

      Category:

      Tags: FAQ

      Emerging lower-voltage, modular SVC and STATCOM applications used for renewables integration and localized power quality issues on the distribution grid.

  • What are solar transformers?

      Solar transformers covers a broad selection of transformers which are designed for the unique requirements of a solar power system. These transformers can include solar inverter transformers, grid tie transformers and zig-zag autotransformers or isolation transformers specially designed to be used in grounding banks for utility hook-ups. Transformers used to directly deliver power to utilities must often be capable of bidirectional current flow.

  • What is Temperature Rise?

      Category:

      Tags: temperature, winding

      It is the increase over ambient temperature of the winding due to energizing and loading

  • What is a Type 2-S enclosure?

      Category:

      Tags: enclosed, NEMA

      This enclosure is the sprinkler proof version of the Type 2.

  • What is a Type 12 enclosure?

      Category:

      Tags: enclosed, NEMA

      This is a non-ventilated indoor enclosure designed primarily for providing a degree of protection against circulating dust, falling dirt, and dripping non-corrosive liquids. This enclosure is both oil and rust resistant suitable for applications such as oil refineries where oil or other chemical liquids may be prevalent. (Note: not watertight)

  • What is a Type 1-N enclosure?

      Category:

      Tags: enclosed, NEMA

      This is a general-purpose non-ventilated enclosure for indoor use primarily designed to provide a degree of protection against limited amounts of falling dirt. It is ideal for normal factory environments.

  • What are Low Temperature Rise Transformers?

      Category:

      Tags: temperature

      All transformers have operating losses, and heat is the product of these losses. Hammond low temperature rise transformers are designed with reduced 115°C or 80°C full load operating temperature rises. These units decrease total operating losses by 20% and 35% respectively, compared with the standard 150°C rise operating system. Hammond low temperature rise transformers provide greater efficiency under normal operating conditions, and overload capability without harm to their service life or reliability.

  • Explain the K-Factor rating?

      Category:

      Tags: k-factor

      K factor is defined as a ratio between the additional losses due to harmonics and the eddy current losses at 60Hz. It is used to specify transformers for non-linear loads. Transformers with a rated K factor of 4, 9, 13, 20 are available. For balanced loading, a transformer with a K factor of 4 should be specified when no more than 50% of the total load is non-linear. A transformer with K factor 9 should be specified when 100% of the load is non-linear. For critical applications, K=13 can be considered.

      As the K-factor of the transformer increases, generally the size and cost increase, low load efficiency (<25% load) decreases and impedance decreases. That is the trade-off to be able to handle higher harmonic factors.

      Learn more about HPS Sentinel K

      Learn more about HPS Sentinel H

  • Iron core motor starting reactor – definition
  • Interphase reactor – definition

      An iron core reactor that gets connected between two rectifier bridges for optimum performance in ANSI circuits 31, 31A, 35, 35A, 41, 42, 45 to 48, 50 to 57.

  • What is an incoming line interrupter switch (electrical disconnect)?

      Category:

      Tags: medium voltage

      This is typically a two position, three phase switch designed to disconnect a transformer on the line side. The switch may or may not also have fuses. The switch assembly is typically attached directly to the transformer enclosure and electrically connected through close coupled bussing.

  • What is an Induced Voltage test?

      Category:

      Tags: tests

      The induced voltage test is applied for 7200 cycles or 60 seconds whichever is shorter. The voltage applied is twice the operating voltage, and confines the integrity of the insulation

  • What are Impedance Voltage and Load Loss tests?

      Category:

      Tags: tests

      The voltage required to circulate the rated current under short-circuit conditions when connected on the rated voltage tap, is the impedance voltage. Rated current is circulated through the windings with the secondary short-circuited. The impedance voltage and load loss is measured. They are corrected to rise +20°C reference temperature.

      Note: This is a standard test only on units over 500kVA. It will only be carried out on lower kVA units when specifically requested.

  • What are Harmonics?

      Category:

      Tags: harmonics

      Harmonics, in an electrical system, are currents created by non-linear loads that generate non-sinusoidal (non-linear) current waveforms. These current and voltage wave forms operate on frequencies that are in multiples of the fundamental 60hz frequency. That is, the fundamental frequency is at 60 hertz, the 2nd harmonic is at 120hz frequency (60 x 2), the 3rd at 180 hertz, and so forth. Harmonics are principally the by-product of switch-mode power supply technology where AC is rectified to DC, and back again. In the process, a capacitor is charged in the first half-cycle, and then discharged in the next half-cycle, in supplying current to the load. This cycle is repeated. This action of recharging causes AC current to flow only during a portion of the AC voltage wave, in abrupt pulses. These abrupt pulses distort the fundamental wave shape causing distortion to the various harmonic frequencies.

  • What is a Fan Cooled transformer?

      Category:

      Tags: temperature

      A transformer cooled mechanically to maintain its rated temperature rise, typically using auxiliary fans to accelerate heat dissipation.

  • What is an exciting or excitation current?

      A transformer exciting current is the current or amperes required to energize the core. Even with zero load, a transformer will draw a small amount of current due to internal loss. The excitation current is made up of two components. The real component in the form of losses that are commonly referred to as no-load losses. The second form is reactive power measured in KVAR.

  • What are Energy Efficient (TP1) Transformers?

      Category:

      Tags: energy efficiency

      TP1 was often used to generically refer to the minimim efficiency levels that were originally require in Canada in 2005 and in the U.S. in 2006 for low voltage ventilated transformers. Specifically, the TP1 specification covers energy efficiency in transformers based on the NEMA Standards Publication, TP-1-1996, “Guide for Determining Energy Efficiency for Distribution Transformers”. The TP1’s recomendations did consider the total owning cost of ownership unique for industrial or commercial installations. TP1 is measured per TP2 and displayed on the nameplate per TP3.

      The TP1 specifcations have now been replaced by higher efficiency specifications:

      • U.S.A.: DOE 2016 efficiency levels (January 1st, 2016)
      • Canada: NRCan 2019 efficiency levels (May 1st, 2019)

  • What are Encapsulated Transformers and where are they used?

      Category:

      Tags: encapsulated

      Encapsulated units are covered in a thicker coating of insulation than typical. Often the coils are completely encased in epoxy or an epoxy and aggregate mixture. Sometimes they are referred to as “potted” or “cast coil”.

      The encapsulated design is especially suited for installations in harsh environments where dust, lint, moisture and corrosive contaminants are present. Typical applications include: pulp and paper plants; steel mills; food processing plants; breweries; mines; marine and shipboard installations.

  • What is an “Electrostatic Shield”?

      Category:

      Tags: winding

      Electrostatically shielded (Faraday Shield) transformers provides a copper electrostatic shield between the primary and secondary windings. The shield is grounded and thus shunts some noise and transients to the ground path rather than passing them through to the secondary. Transformers having a K-Rating are required to have an electrostatic shield.

      Electrostatically shielded transformers often preferred for electrical installations where electronic circuitry operating at low voltage DC is present and is very sensitive to ‘noise’. Recent testing of electrostatically shielded transformers has questioned their perceived effectiveness where the transformer’s secondary is grounded which would cover most applications.

  • What is the “Efficiency” of a transformer?

      Category:

      Tags: energy efficiency

      The percentage of power transferred from the input of equipment to the output of equipment in Watts. (power out/power in x 100)

  • Shunt reactor – definition
  • What is a Type 3R-E enclosure?

      Category:

      Tags: enclosed, NEMA

      Although similar to the Type 3R enclosure, a Type 3RE also provides added protection against snow and particulate materials. It is more suitable for outdoor installations where snow or other particulate materials are present. In certain conditions, where sustained high wind conditions exist (typically > 75-80 km/hour), external measures to reduce the flow of snow and/or particulate materials may be required. Please consult HPS for assistance with applications where sustained high wind conditions exist.

  • What is a Type 1 enclosure?

      Category:

      Tags: enclosed, NEMA

      This is a general-purpose ventilated enclosure for indoor use primarily designed to provide a degree of protection against limited amounts of falling dirt. It is ideal for normal factory environments.

  • What is a solar grounding bank?

      A grounding bank is used to ground a solar application and typically must meet IEEE P1547.8 requirements. The magnetic portion of this typically takes the form of either a zig-zag or Wye-N to Delta transformer. The size of these transformers are typically dependent on a number of parameters unique to each installation.

  • What is a Ventilated enclosure?

      Category:

      Tags: enclosed

      A ventilated enclosure is constructed to provide circulation of external air through the enclosure to remove excess heat.

  • What is a Polarity and Phase-Relation test for?

      Category:

      Tags: tests

      Polarity and phase-relation tests are made to determine angular displacement and relative phase sequence to facilitate connections in a transformer. Determining polarity is also essential when paralleling or banking two or more transformers.

  • What is an Open Delta transformer?

      Category:

      Tags: delta, three phase

      An open delta transformer is a three phase transformer that only has two primary and secondary windings, with one side of the delta phase diagram “open”. Open delta transformers are rare and are typically only used for small loads where cost is important. More common is critical loads being wired with three single phase transformers in a banked configuration. Should one of these transformers fail, the three phase circuit can remain active although the two remaining transformers are limited to about 57% of the total load. This allows a circuit to remain powered during a failure of a transformer, albeit at a lower overall load factor.

      Open Delta

  • What is a pad mounted transformer?

      A pad mounted transformer typically refers to a specific style of enclosure for larger transformers that is capable of being installed in areas accessible to the general public. The transformer will typically have features including tamper resistant construction, tamper proof bolts and screws, lockable compartments with hinged doors, bottom entry of primary and secondary cabling and baffled ventilation openings if applicable. These should not be confused with the general statement that electrical transformers are often installed on a concrete pad.

  • What is Nomex®?

      Category:

      Tags: insulation

      Nomex is a brand name of DuPont and provides lightweight, heat and flame-resistant electrical insulation for transformers for insulation systems up to 220C.

  • What are Non-Linear Loads?

      Category:

      Tags: non-linear

      Today, non-linear loads make up a large percentage of all electrical demand. Rectified input, switching power supplies and electronic lighting ballasts are the most common single-phase non-linear loads. Harmonic currents and voltages produced by single phase, non-linear loads which are connected phase-to-neutral in a three phase four wire system, are third order, zero sequence harmonics (the third harmonic and its odd multiples – 3rd, 9th, 15th, 21st, etc., phasors displaced by zero degrees). These third order, zero sequence harmonic currents, do not cancel but add up arithmetically on the neutral bus, creating a primary source of excessive neutral current.

  • Neutral grounding reactors – definition
  • What is NEMA TP3?
  • What is NEMA ST 20?
  • What is NEMA TP2?

      NEMA TP2 defines how energy efficiency is measured. Typically, it uses a sinusoidal wave with no harmonics at unity (1.0) power factor at 35% load for 600 volt class units and 50% load for medium voltage units.

      This regulation has been replaced by similar test standards described in DOE 2016 and NRCan 2019 regulations.

  • What are Medium Voltage Transformers and where are they used?

      Category:

      Tags: medium voltage

      Medium voltage transformers that have one or more windings above 1.2 k-volts. Ventilated medium voltage transformers up to 2500 kVA are covered by DOE 2016 efficiency regulation in the U.S.A. and up to 5000 kVA by NRCan 2019 efficiency regulations in Canada.

      They are primarily for use in stepping down medium voltage power to a lower operating voltage for commercial, institutional or industrial applications. However, medium voltage transformers may also be used to step-up voltage.

  • What does is a reconnectable transformer?

      Category:

      Tags: medium voltage, taps

      A reconnectable transformer typically refers to a transformer with two primary connections. These may be used for mobile equipment, test transformers or to accommodate future voltage changes and upgrades in a facility without having to change the transformer. Depending on the difference in voltages and application reconnectable transformers may be exempt from current efficiency regulations.

  • Are obsolete TP1/C802.2 transformers still available in North America?

      TP1 transformers built and in the U.S.A. before January 1st, 2016 can still be sold and installed in the U.S.A. At the time of this writing, stocks of new TP1 transformers are no longer readily available but may still be found in the used market.

      In Canada, NRCan 2019 will ban manufacturers from selling transformers after May 1st, 2019 which don’t meet the new 2019 efficiency regulations. Older C802.2 units can still be sold by distributors and installed after the regulations.

  • What are Dielectric tests?

      Category:

      Tags: tests

      The purpose of dielectric tests is to demonstrate that the transformer has been designed and constructed to withstand the voltages associated with specified insulation levels.

  • DC smoothing reactor – definition
  • Current limiting reactor – definition

      Category:

      Tags: performance

      An air core reactor that limits the short circuit fault current to a manageable value.

  • What is Core Loss?

      Category:

      Tags: loss

      Losses in watts caused by magnetization of the core and its resistance to magnetic flux when excited or energized at rated voltage and frequency. Also referred to as excitation loss or no-load loss.

  • What is Coil Hot-Spot Temperature?

      Category:

      Tags: temperature

      It is the absolute maximum temperature present in the transformer. This number is equal to the sum of the ambient temperature, temperature rise and a variable.

      T Hot Spot = T ambient + T rise + (10-20) °C.

  • What is the International Building Code?

      Category:

      Tags: regulation

      The International Building Code (IBC) is a model building code developed by the International Code Council (ICC). It has been adopted for use as a base code standard by most jurisdictions in the United States. The IBC addresses both health and safety concerns for buildings based upon prescriptive and performance related requirements. The IBC is fully compatible with all other published ICC codes. The code provisions are intended to protect public health and safety while avoiding both unnecessary costs and preferential treatment of specific materials or methods of construction.

  • What is Subtractive Polarity?

      Category:

      Tags: single phase

      The relative polarities of voltages on single phase transformers is important when using the two units in parallel or connecting two or three units to create a three phase bank. Most single phase transformers are wired in Additive Polarity. Visualize two primary terminals H1 and H2 on top of a square representing a single phase transformer. Now visualize two secondary terminals, X1 and X2. If X2 is on the left size and X1 is on the right side, (reading X2 – X1 left to right) then this would be additive polarity. If the terminal X1 is on the left side and X2 is on the right side (reading X1-X2 left to right) then this would be subtractive polarity.

      Most single phase wiring diagrams have a dot on both the primary and secondary sides, typically on the H1 and X1 terminals. This dot represents the matching polarity on the primary and secondary sides of the single phase transformer. When wiring single phase units in parallel or banking, the polarities of the transformers used must be kept consistent.

  • What is NFPA (National Fire Protection Association)?

      The National Fire Protection Association (NFPA) is a United States trade association, albeit with some international members, that creates and maintains private, copyrighted standards and codes for usage and adoption by local governments.

      NFPA 70E covers the Standard for Electrical Safety in the Workplace.

  • What is meant by “Class” in insulation?

      The insulation rating is the maximum allowable winding (hot spot) temperature of a transformer operating at an ambient temperature of 40°C. Insulation systems are classified by the temperature rating. The following table summarizes the different insulation systems available.

      Insulation Rating

      Insulation Class

      Average Winding Temperature Rise

      Hot Spot Temperature Rise

      Maximum Winding Temperature

      Class 105 A 55 degree C 65 degree C 105 degree C
      Class 150 or 130 B 80 degree C 110 degree C 150 degree C
      Class 180 F 115 degree C 145 degree C 180 degree C
      Class 200 N 130 degree C 160 degree C 200 degree C
      Class 220 H 150 degree C 180 degree C 220 degree C
               
      Note: the maximum acceptable temperature rise based on an average ambient of 30 degree C during any 24 hour period and a maximum ambient of 40 degree C at any time.

  • What is IR drop?

      Category:

      Tags: winding

      IR drops relates to Ohm’s Law: Voltage = Current x Resistance. Transformers utilize conductors which have resistance and can cause a slight voltage drop. Typically manufacturers compensate the winding ratio to mitigate any effects of IR voltage drop in the secondary voltage.

  • What is an audio transformer?

      Category:

      Tags: Impedence

      Audio transformers are typically electronic transformers used in microphone and amplifier applications. Audio transformers are typically rated by power (VA), frequency response and distortion. They are often essential in impedance (power) matching functions.

      HPS does not manufacturer audio transformers and is often confused with Hammond Manufacturing at https://www.hammfg.com.

  • What is Additive Polarity?

      Category:

      Tags: single phase

      The relative polarities of voltages on single phase transformers is important when using the two units in parallel or connecting two or three units to create a three phase bank. Most single phase transformers are wired in Additive Polarity. Visualize two primary terminals H1 and H2 on top of a square representing a single phase transformer. Now visualize two secondary terminals, X1 and X2. If X2 is on the left size and X1 is on the right side, (reading X2 – X1 left to right) then this would be additive polarity. If the terminal X1 is on the left side and X2 is on the right side (reading X1-X2 left to right) then this would be subtractive polarity.

      Most single phase wiring diagrams have a dot on both the primary and secondary sides, typically on the H1 and X1 terminals. This dot represents the matching polarity on the primary and secondary sides of the single phase transformer. When wiring single phase units in parallel or banking, the polarities of the transformers used must be kept consistent.

  • What is a vault room?

      Category:

      Tags: regulation

      A vault room is a reinforced concrete structure used for the purpose of housing liquid cooled transformers, switchgear and other electrical distribution equipment. Requirements for vault rooms for liquid filled transformers are defined by many specifications including NEC 450.26. Vault requirements are outlined in NEC 450, Part III, beginning with 450.4. Typical requirements might include:

      • Ventilation with outside air via a dedicated ductwork
      • Three hour fire-resistant construction including a minimum 4″ concrete floor
      • Oil containment capable of containing the entire liquid contents of the largest transformer
      • Some exceptions will allow lower construction standards such as the use of sprinklers, carbon dioxide or halon systems and/or the use of “less flammable” liquids.

  • What is a Epoxy Cast transformer?

      Category:

      Tags: cast coil

      A transformer with coils solidly cast in epoxy resin under vacuum in a mold. Also called cast resin or cast coil transformers.

  • What is a Non-ventilated enclosure?

      Category:

      Tags: enclosed

      A non-ventilated enclosure is constructed to restrict unintentional circulation of external air through the enclosure. Common industry descriptions would include Type 12, 4 and 4X in North America.

  • What is a Cast Resin transformer?

      Category:

      Tags: cast coil

      A transformer with coils solidly cast in epoxy resin under vacuum in a mold. Also called cast coil or epoxy cast coil transformers.

  • What does Readily Accessible mean?

      Category:

      Tags: regulation

      Per 1.2.2 of NEMA ST-20, Capable of being reached quickly for operation, renewal, or inspections, without requiring those to whom ready access is requisite to climb over or remove obstacles or to resort to portable ladders, chairs, etc.

  • What does MSR stand for?
  • What does LV stand for?
  • What is a Type 2 enclosure?

      Category:

      Tags: enclosed, NEMA

      This is a general-purpose enclosure for indoor use primarily to provide a further degree of protection against limited amounts of falling water (drip proof) and dirt.

  • What does 50/60 Hertz mean?

      Transformers that are designed to specifically run at 60 Hz can’t be run at 50 Hz or in some cases only with significant derating. Magnetic flux is proportional to frequency so a 50 Hz transformer has a core 20% larger to handle 20% more magnetic flux than a 60 Hz unit. A 50 Hz transformer will simply run cooler at 60 Hz given the proper voltage is applied. Transformers cannot change frequency, the primary frequency equals the secondary frequency.

  • What is a Unit Substation Style Transformer (USST)?

      A Unit Substation Style Transformer (USST) is typically defined as a transformer with a medium voltage primary and with either or both the primary and secondary close coupled through bussing to switchgear assemblies.

  • What is U.L. 1562?

      U.L. 1562 covers medium voltage dry-type transformers:

      1.1 These requirements cover single-phase or three-phase, dry-type, distribution transformers, including solid cast and resin encapsulated transformers. The transformers are provided with either ventilated or non-ventilated enclosures and are rated for a primary or secondary voltage from 601 to 35000 V.

      1.2 These transformers are intended for installation in accordance with the National Electrical Code, ANSI/NFPA 70.

      1.3 These requirements do not cover the following transformers:

      1. Instrument transformers
      2. Step-voltage and induction voltage regulators
      3. Current regulators
      4. Arc furnace transformers
      5. Rectifier transformers
      6. Specialty transformers (such as rectifier, ignition, gas tube sign transformers, and the like)
      7. Mining transformers
      8. Motor-starting reactors and transformers

      1.4 These requirements do not cover transformers under the exclusive control of electrical utilities utilized for communication, metering, generation, control, transformation, transmission, and distribution of electric energy regardless of whether such transformers are located indoors, in buildings and rooms used exclusively by utilities for such purposes; or outdoors on property owned, leased, established rights on private property or on public rights of way (highways, streets, roads, and the like).

  • What is U.L. 1561?

      UL1561 covers 600 Volt Class Transformers:

      1.1 These requirements cover:

      1. General purpose and power transformers of the air-cooled, dry, ventilated, and non-ventilated types to be used in accordance with the National Electrical Code, ANSI/NFPA 70. Construction types include step up, step down, insulating, and autotransformer type transformers as well as air-cooled and dry-type reactors

      OR

      1. General purpose and power transformers of the exposed core, air-cooled, dry, and compound-filled types rated more than 10 kVA to be used in accordance with the National Electrical Code, ANSI/NFPA 70. Constructions include step up, step down, insulating, and autotransformer type transformers as well as air-cooled, dry, and compound-filled type reactors.

      1.2 These requirements do not cover ballasts for high intensity discharge (HID) lamps (metal halide, mercury vapor, and sodium types) or fluorescent lamps, exposed core transformers, compound-filled transformers, liquid-filled transformers, voltage regulators, general use or special types of transformers covered in requirements for other electrical equipment, autotransformers forming part of industrial control equipment, motor-starting autotransformers, variable voltage autotransformers, transformers having a nominal primary or secondary rating of more than 600 volts, or overvoltage taps rated greater than 660 volts.

      1.3 These requirements do not cover transformers provided with waveshaping or rectifying circuitry. Waveshaping or rectifying circuits may include components such as diodes and transistors. Components such as capacitors, transient voltage surge suppressors, and surge arresters are not considered to be waveshaping or rectifying devices.

  • What is a Type 4X enclosure?

      Category:

      Tags: enclosed, NEMA

      This enclosure is the same as the Type 4, and is also corrosion resistant. It is ideal for environments such as food processing plants and refineries.

  • What is a Type 4 enclosure?

      Category:

      Tags: enclosed, NEMA

      Type 4 is a non-ventilated indoor or outdoor enclosure designed primarily to provide a degree of protection against windblown dust and rain, splashing water, hose-directed water, and damage from external ice formation.

      It is suitable in areas where exposure to large amounts of water from any direction. (Note: not submersible)

  • What is a Type 3R enclosure?

      Category:

      Tags: enclosed, NEMA

      Similar to the Type 3, it is also intended for outdoor use. It provides a greater degree of protection against rain, sleet, falling snow or dirt and damage from external ice formation. It is typically used for outdoor installations where no blowing snow or conductive dust exists.

  • What is a Type 3 enclosure?

      Category:

      Tags: enclosed, NEMA

      This is a general purpose ventilated enclosure for outdoor use designed primarily to provide a degree of protection against rain, sleet, wind blown snow or dust and damage from external ice formation. It is considered ideal for construction sites, subways etc.

  • What is a triplex transformer?

      Category:

      Tags: three phase, winding

      A triplex transformer is composed of three separate single phase transformers which are banked and connected directly together to form a single three phase unit in a common enclosure. While slightly larger than a dedicated three phase unit. a triplex design can be broken down into three significantly smaller and lighter components when there are size and/or weight restrictions for transporting the transformer. These are often used in mining or high rise building installations where the unit must be transported in an elevator.

  • What is ANSI C57.12.01?
  • What is rodent screening?

      Rodent screens are added over ventilation openings of transformers to prevent rodents from entering the compartment. Large transformers installed directly on concrete pads may also need a steel bottom added. Rodent screens will not prevent the entry of dust or insects.

  • RC filter reactor – definition
  • How can I disinfect my electrical transformer from COVID-19?

      Category:

      Tags: FAQ

      Reference the NEMA GD 4-2020 guide; COVID-19 Cleaning and Disinfecting Guidance for Electrical Equipment.

      Click HERE to access the guide. 

       

  • How to transformer taps adjust voltage?

      Category:

      Tags: winding

      The ratio between the number of windings in the primary and secondary coil’s of a transformer determines the voltage ratio. If a transformer has 100 primary windings and 25 secondary windings, the ratio is 100:25 = 4:1. If the primary is fed with 480VAC, the ratio of primary to secondary voltage is 4:1 or 480:120. Taps are used to adjust for voltage differences at the transformer’s primary winding.A 5% adds or subtracts 5% of the windings.

  • How do Harmonic Mitigating Transformers save energy?

      Category:

      Tags: harmonics

      Harmonic Mitigating Transformers reduce harmonic losses in the following ways:

      1. Zero phase sequence harmonic fluxes are cancelled by the transformer’s secondary windings. This prevents triplen harmonic currents from being induced into the primary windings where they would circulate. Consequently, primary side I2R and eddy current losses are reduced.

      2. Multiple output HMTs cancel the balanced portion of the 5th, 7th and other harmonics within their secondary windings. Only residual, unbalanced portions of these harmonics will flow through to the primary windings. Again I2R and eddy current losses are reduced.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • How do Harmonic Mitigating Transformers reduce voltage distortion?

      Category:

      Tags: harmonics, Wye

      Delta-wye transformers, even those with a high K-factor rating, generally present high impedance to the flow of harmonic currents created by the non-linear loads. Non-linear loads are current sources that push the harmonic currents through the impedances of the system. Any voltage drop across the impedance of the transformer at other than the fundamental frequency (60 Hz) is a component of voltage distortion.

      Because of its higher impedance to harmonic currents, the voltage distortion at the output of a delta-wye transformer often reaches the 8% maximum voltage distortion limit recommended by IEEE Std. 519-2014 by the time that the secondary side load has reached just one-half of full-load RMS current. At closer to full-load, these transformers can produce critically high levels of voltage distortion and flat-topping at their outputs and at the downstream loads.

      To minimize the voltage distortion rise due to the transformer itself, Harmonic Mitigating Transformers (HMTs) are designed to reduce the impedance seen by the harmonic currents. This is accomplished through zero sequence flux cancellation and through phase shifting. The secondary winding configuration of the HMT cancels the zero sequence fluxes; those produced by the 3rd, 9th, 15th (triplen) current harmonics, without coupling them to the primary windings.

      This prevents the triplen current harmonics from circulating in the primary windings as they do in a delta-wye transformer. The flux cancellation also results in much lower impedance to the zero sequence currents and hence lower voltage distortion at these harmonics. In addition, the reduced primary winding circulating current will lower losses and allow the transformer to run cooler.

      The remaining major harmonics (5th, 7th, 11th, 13th, 17th & 19th) are treated to varying degrees through the introduction of phase shifts in the various HMT models.

      Single output HMTs are offered in 0° and -30° models to provide upstream cancellation of 5th, 7th, 17th and 19th harmonic currents on the primary feeder.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What are High Voltage and Low Voltage windings?

      These terms are used to distinguish the winding having the greater voltage rating from that having the lesser in two winding transformers.

  • What is involved with Grounds or Grounding?

      Category:

      Tags: grounding, impedance

      Connecting one side of a circuit to the earth through low resistance or low impedance paths

  • What is a Grounding Transformer?

      Category:

      Tags: grounding

      It is a special three-phase autotransformer for establishing a neutral on a 3-wire delta secondary. Also referred to as a Zig-zag transformer.

  • Explain the term Phase?

      It is a type of AC electrical circuit; usually single phase 2-wire or 3-wire, or three-phase, 3 or 4 wire.

  • What is Voltage Regulation?

      Category:

      Tags: regulation

      Voltage regulation is the difference between the transformer secondary No-Load and Full-Load voltage with respect to its Full-Load voltage.  Essentially, every transformer has a voltage drop caused by its own impedance (which is composed of its winding resistive and inductive properties).  Therefore, at different voltages and loading conditions, this internal voltage drop across the transformer windings will vary and ultimately will affect the final secondary output voltage.

  • What is the difference between Ethernet and Ethernet/IP?

      Category:

      Tags: FAQ

       Ethernet is the physical networking (link layer) protocol where the connection is actually made, while Ethernet/IP is an industrial communications protocol (application layer).  Ethernet/IP combines the physical Ethernet cabling, Internet Protocol (IP) for networking within it's application layer protocol.  Ethernet/IP can be used in HPS products such as HPS TruWave and various meters.

  • What does ONAN mean?

      Category:

      Tags: heat

      “Oil Natural Air Natural” – Natural convectional circulates the flow of oil for cooling.

  • What does ONAF mean?

      Category:

      Tags: heat

      “Oil Natural Air Forced” – Natural convectional circulates the flow of oil for cooling.  Fan forced air is applied to the cooling surface of the enclosure to improve cooling.

  • What does OFAF mean?

      Category:

      Tags: heat

      “Oil Forced Air Forced” – Fan forced air is applied to the cooling surface of the enclosure to improve cooling.  In addition, an oil pump further forces additional oil flow to aid in cooling.

  • What are No-Load Losses (Excitation Losses)?

      Category:

      Tags: loss

      It is the loss in a transformer that is excited at rated voltage and frequency, but without a load connected to the secondary. No-load losses include core loss, dielectric loss, and copper loss in the winding due to exciting current.

  • What are NEMA Premium Efficiency Transformers?

      Category:

      Tags: performance

      NEMA Premium provides 30% fewer losses than the 2006 DOE 10 CFR Part 431 (commonly called TP1) or Canadian C802.2. This covers low voltage distribution transformers and is measured at 35% load.

      NEMA Premium is largely obsolete as a term and has been replaced by similar efficiencies in the U.S.A’s DOE 2016 and Canada’s NRCan 2019 energy efficieny regulations. NEMA no longer promotes the NEMA Premium specification or specifications higher than the current DOE 2016 and NRCan 2019 levels.

  • What are the most common power problems?

      Category:

      Tags: voltage transients

      Research conducted by both IBM and Bell indicates that most line disturbances to sensitive equipment are line noise and voltage fluctuations.

  • What is a Mid-tap?

      Category:

      Tags: taps

      It is a reduced capacity tap midway in a winding, also referred to as a ‘Center tap’. Usually it is in the secondary winding.

  • What is Zone Classification?

      Category:

      Tags: regulation, tests

      Obsolete versions of seismic standards used to classify seismic areas ranging from zone 0 to zone 4, where zone 0 indicates the weakest earthquake ground motion and zone 4 indicates the strongest. The zone classification is no longer used. The current standards specify the Sds design earthquake spectral response acceleration parameter as described above.

      Please refer link https://seismicmaps.org/ to determine the Sds criteria for a specific location.

  • Who Needs Seismic?

      Category:

      Tags: regulation, tests

      Healthcare facilities and emergency response locations, including police stations and other vital government facilities, will often include a Seismic Certification requirement. Power generation stations may also have this requirement as well as facilities handling hazardous, toxic or explosive materials.

      To determine the Sds criteria for a specific location, the U.S. Geological Survey provides a utility on their website, which can be viewed at https://seismicmaps.org/

  • Where is a Scott-T Transformer used?

      Category:

      Tags: three phase

      Typical applications for a Scott-T transformer include:

      • Used in an electric furnace installation where it is needed to operate two single-phase feeds and draw a balanced load from the three-phase supply.
      • Used to supply the single phase loads such as traction power. This helps to keep the load on the three-phase system as nearly balanced as possible.
      • Used to link a 3-phase system with a two–phase system with the flow of power in either direction.

      The Scott-T connection permits conversions of a 3-phase system to a two-phase system or vice versa. Since 2-phase generators are not available, the conversion from two phases to three phases is not a practical application.

  • What problems can occur if I undersize the short circuit protection on a transformer?

      Category:

      Tags: performance

      Nuisance tripping is a concern when short circuit protection is undersized from the National Electric Code recommendations in NEC 450.3.  All transformers experience an inrush current during any energization. The inrush current results from the transformer establishing the initial electromagnetic field and is not linked to load. If short circuit protection is undersized, there is a chance for nuisance tripping of fuses and circuit breakers anytime the transformer is energized.

  • What is the lowest temperature transformers can be stored in?

      Category:

      Tags: heat, temperature

      Dry-type transformers with the exception of Cast Coil (HPS Endura Coil) can be stored to temperatures of -50 degrees C. Cast Coil Transformers can only be stored to temperatures of -20C. If a standard cast coil transformer is stored below -20C, the epoxy coils can crack. Transformers which are energized before 0C can be run in ambient temperatures to -40C.

      There are two main concerns with low temperatures occuring during storage when the units are not energized. Energized transformers have load and no-load losses which will keep the core and coils operational to -40C:

      • Contraction and Expansion of the core and coil during low temperatures can crack or damage the insulation.
      • Cold temperatures can cause condensation to form on the transformer which can result in short circuits and insulation damage.

      The minimum ambient temperature designed for is -40C based on the Environment Canada data Extreme Minimum Temperatures for Wiarton, ON (-36.4C on 18-Jan-1977) and Lucknow, ON (-36.7C on 05-Feb-1918). If the temperature of a transformer’s core and coil is below -25C (typically during unenergized storage), please consult HPS for the cold start procedure before any energization. If the temperature of a transformer is below 0C, please follow the HPS Cold Start Procedure. It is recommended that the transformer be meggered to make sure it has a minimum value of 100 Megaohm before energization after storage.

  • What is the lowest temperature transformers can be energized?

      Category:

      Tags: temperature

      Dry-type transformers with the exception of Cast Coil (HPS Endura Coil) can be stored to temperatures of -50 degress C. Cast Coil Transformers can only be stored to temperatures of -20C. If a standard cast coil transformer is stored below -20C, the epoxy coils can crack. Transformers which are energized before 0C can be run in ambient temperatures to -40C.

      There are two main concerns with low temperatures occur during storage when the units are not energized. Energized transformers have load and no-load losses which will keep the core and coils operational to -40C:

      • Contraction and Expansion of the core and coil during low temperatures can crack or damage the insulation.
      • Cold temperatures can cause condensation to form on the transformer which can result in short circuits and insulation damage.

      The minimum ambient temperature designed for is -40C based on the Environment Canada data Extreme Minimum Temperatures for Wiarton, ON (-36.4C on 18-Jan-1977) and Lucknow, ON (-36.7C on 05-Feb-1918). If the temperature of a transformer’s core and coil is below -25C (typically during unenergized storage), please consult HPS for the cold start procedure before any energization. If the temperature of a transformer is below 0C, please follow the HPS Cold Start Procedure. It is recommended that the transformer be meggered to make sure it has a minimum value of 100 Megaohm before energization after storage.

  • What is the induction principle of transformers?

      A transformer consists of laminated silicon steel cores on which one or more coils of wire have been wound. The two windings are electrically isolated from each other (with the exception of autotransformers) and usually have widely different numbers of turns.

      If the transformer primary is connected to an A.C. power source of suitable voltage, a small no-load current called the exciting current will flow into the coil and produce a magnetic flux in the iron core. Since the source is A.C., the flux will also be alternating. This alternating magnetic flux links the secondary turns and induces a small voltage in each turn. The induced volts per turn of the secondary windings adds to appear across the secondary terminals. It should be understood that the flux induces a voltage in each primary turn equal to that in each secondary turn. The difference between the total induced primary voltage and the applied voltage is approximately equal to the IR drop. The ratio of turns between the primary and secondary coils determines the output voltage.

  • What is the hot spot allowance of a transformer?

      Category:

      Tags: heat

      The coils of a transformer core do not evenly heated during energization. Parts of one coil will be hotter than the surrounding areas because they are farther from any ventilated openings or closer to the core which also produces heat. The hot spot allowance is a set number as defined by industry standards and is associated with the insulation class. Typically the smaller the transformer, the lower the insulation class and the more uniform the heating.

      • 105C Insulation System: 10C Hot Spot Allowance
      • 150C Insulation System: 30C Hot Spot Allowance
      • 180C Insulation System: 25C Hot Spot Allowance
      • 220C Insulation System: 30C Hot Spot Allowance

      The Hot Spot Allowance is added the expected ambient temperature and full load temperature rise to get the total expected temperature rise of a transformer.

  • What is a SMPS and how does it generate harmonics?

      Category:

      Tags: harmonics

      The Switch-Mode Power Supply (SMPS) is found in most power electronics today. Its reduced size and weight, better energy efficiency, and lower cost make it far superior to the power supply technology it replaced.

      Electronic devices need power supplies to convert the 120VAC receptacle voltage to the low voltage DC levels that they require. Older generation power supplies used large and heavy 60 Hz step-down transformers to convert the AC input voltage to lower values before rectification. The SMPS avoids the heavy 60 Hz step-down transformer by directly rectifying the 120VAC using an input diode bridge. The rectified voltage is then converted to lower voltages by much smaller and lighter switch-mode dc-to-dc converters using tiny transformers that operate at very high frequency. Consequently the SMPS is very small and light.

      The SMPS is not without its downside, however. The operation of the diode bridge and accompanying smoothing capacitor is very nonlinear in nature. That is, it draws current in nonsinusoidal pulses at the peak of the voltage waveform. This non-sinusoidal current waveform is very rich in harmonic currents.

      Because the SMPS has become the standard computer power supply, they are found in large quantities in commercial buildings. Acting together, the multitude of SMPS units can badly distort what started out as a sine wave voltage waveform.

      Twice per cycle every SMPS draws a pulse of current to recharge its capacitor to the peak value of the supply voltage. Between voltage peaks the capacitor discharges to support the load and the SMPS does not draw current from the utility. The supply voltage peak is flattened by the instantaneous voltage drops throughout the distribution system caused by the simultaneous current pulses drawn by the multiple SMPS units. The expected sine wave with a peak of 120 x √2 = 169.4V instead starts to resemble a square wave. The flattened voltage waveform contains a lowered fundamental voltage component plus 3rd, 5th, 7th, 9th and higher voltage harmonics.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What is RCBN – Reduced Capacity Below Nominal?

      Category:

      Tags: taps

      For transformer equipped with primary or secondary taps designed for RCBN, the customer is permitted to connect to a lower voltage tap (BELOW NOMINAL), provided that the customer load capacity (KVA) is also REDUCED so as to ensure that the rated winding current does not exceed its nominal value.

  • What is Overload?

      Category:

      Tags: overload

      Overload is when a transformer is subjected to voltages and/or currents that exceed its design specifications. Transformer voltages and current limits are typically governed by their nameplate specifications.

  • What is NFPA 70E?

      NFPA 70E is the titled Standard for Electrical Safety in the Workplace, is a standard of the National Fire Protection Association (NFPA). The document covers electrical safety requirements for employees. The NFPA is best known for its sponsorship of the National Electrical Code (NFPA 70).

      NFPA 70E addresses employee workplace electrical safety requirements. The standard focuses on practical safeguards that also allow workers to be productive within their job functions. Specifically, the standard covers the safety requirements for the following:

      • Electrical conductors and equipment installed within or on buildings or other structures, including mobile homes, recreational vehicles, and other premises (yards, carnivals, parking lots, and industrial substations)
      • Conductors that connect installations to a supply of electricity
      • Not covered are – electrical installations in marine, aircraft, auto vehicles, communications and electrical utilities.

      Key principles covered are JSA/JHA/AHA procedures to ascertain shock protection boundaries, arc flash incident energy expressed in calories/cm2, lockout-tagout, and personal protective equipment. While the various OSHA, ASTM, IEEE and NEC standard provide guidelines for performance, NFPA 70E addresses practices and is widely considered as the de facto standard for Electrical Safety in the Workplace.

  • Do any performance issues arise during high ambient temperatures?

      Temperatures which exceed the rated ambient temperatures for which the insulation system is designed can cause insulation damage and premature failure. This can often occur in hotter
      environments or in rooms which have inadequate ventilation. Care should be taken in installing stacked transformers because the top transformer may use air that has been heated by the lower unit. Damage from high ambient temperatures often does not cause an immediate failure but can cause damage that results in a failure weeks, months or years later.

      High ambient temperatures can be mitigated several ways:

      • Order a transformer designed with a lower temperature rise.
      • Use fan cooling, this is typically an economical solution when a unit exceeds 500-1500kVA.
      • Place the transformer in a temperature controlled location.
      • Properly ventilate the location that the transformer is located in.

      Never try to use cooling fans directly on a transformer or blow across a transformer’s windings.

      Manufacturers use special fans, specific locations, and cooling patterns to cool transformers. Improper placement of airflow could cause disruption of the convection airflow and cause the transformer to overheat.

  • Do any performance issues arise during low ambient temperatures?

      Generally low ambient temperatures do not affect an energized transformer. No-load losses on an energized transformer typically generate enough heat to operate effectively in temperatures to -20°C or lower.

      The main issue with lower temperatures is when the unit is not energized. Extremely low temperatures or if the transformer heats up too quickly may cause welds and insulation to become brittle and crack, especially if the transformer experiences any mechanical stresses.

      More importantly, low temperatures can cause moisture (dew, frost) to form on the unit. This can be absorbed into the insulation system and not be apparent.

      If ambient goes below -30°C, special designs and cold start procedures may be necessary. Care should be taken to store transformers in dry areas with temperature control. Installation manuals typically suggest that transformers be tested (meggered), brought above 0°C and/or go through a dry-out process if moisture is suspected to be present.

      Damage and injury can result from energizing a transformer which has had its insulation system compromised by moisture.

  • Why Are There Physical Clearance (Distance) Requirements on the Nameplate?

      Category:

      Tags: heat, temperature

      A ventilated transformer’s physical clearance requirements are designed to provide adequate clearance for airflow cooling. Generally, the larger the transformer the more airflow and clearance is needed. The more important areas are the front and back of ventilated transformers where the air may enter in the bottom and exit at the top. Since the sides of distribution transformers generally don’t have ventilation openings, side clearance is less important. There must also be no obstructions that limit airflow into the bottom vents and top clearance from ceilings must also be maintained.

      All smaller clearances should be reviewed by the manufacturer to verify they are adequate. Also note that electrical codes require minimum front panel clearances to allow safe and easy access to the wiring area. Units supplied with factory installed wall-mounting brackets may also have the back closer to the wall than the nameplate requirements; this is acceptable.  These statements may not apply to non-ventilated and/or potted transformers which don’t have ventilation slots and/or may have zero clearance when mounted to wall suing supplied brackets.

  • Define Vacuum Pressure Impregnation?

      Category:

      Tags: VPI

      A vacuum and pressure impregnation process using a resin that is then oven cured to completely seal and protect the surface of a transformer and provides a strong mechanical bond. This process is standard on all HPS transformer products.

  • How does a UPS transformer’s efficiency affect the overall system efficiency?

      ASHRAE 90.4 Section 6.2.1.2.1.1 notes that UPS transformer’s efficiencies at given loads must be included in the total losses for evaluation. Active single feed systems should be evaluated at 100% and 50% ITE load while active dual feed systems should be evaluated at 50% and 25% loads.

  • What is Transverse Mode?

      Category:

      Tags: FAQ

      It is electrical noise or voltage disturbance that occurs between phase and neutral (between lines), or from spurious signals across the metallic hot line and the neutral conductor.

  • What type of transformers does the NEC 2017 require a 1 hour fire seperation barrier?

      Category:

      Tags: regulation, safety

      A 1 hour fire separation barrier is required for any dry type transformer over 112.5 kVA with less than class 155C insulation. As a practical matter, few dry type transformers in this size range utilize insulation systems below 155C. The most common insulation type is 220C.

      The 1 hour fire separation requirement would also apply to liquid-filled transformers specified in Article 450 based on the type of liquid used and other ratings.

  • What are some of the Tests performed on transformers?

      Category:

      Tags: tests

      Normal, routine production tests include:

      1. core loss;
      2. load loss – winding or copper loss;
      3. Impedance;
      4. hi-pot – high voltage between windings and ground;
      5. induced – double induced two times voltage.

      Optional special tests include:

      1. heat run – temperature testing;
      2. Noise tests – sound level measurement;
      3. impulse tests – BIL tests:
      4. partial discharge

  • What is Temperature Class?

      Category:

      Tags: temperature

      It is the maximum temperature that the insulation can continuously withstand.

      The classes of insulation systems in a transformer are rated as follows:

      Class 105°C

      Class 150°C

      Class 180°C

      Class 220°C

  • When is Sound Level an issue in the design?

      Category:

      Tags: sound level

      Sound needs to be considered when transformers are located in close proximity to occupied areas. All energized transformers emanate sound due to the alternating flux in the core. This normal sound emitted by the transformer can be a source of annoyance unless it is kept below acceptable levels. There are ways of minimizing sound emission as discussed in the HPS “Field Service Guide”. HPS  Transformers are built to meet the latest ANSI, CSA and UL standards. These standards are outlined in the accompanying table.

  • Should low voltage system be assessed for arc-flash hazards?

      Category:

      Tags: low voltage

      IEEE 1584-2018 provides mathematical models for designers and facility operators to apply in determining the arc-flash hazard distance and the incident energy to which workers could be exposed during their work on or near electrical equipment.

      It generally indicates that systems with an available short circuit current of 2000 Amps or higher should be assessed for arc-flash potential. A rule of thumb would indicate that most systems fed by a 45 kVA or larger transformer will need to be assessed if impedance (%Z) of 45 kVA is less than 6%, 30 kVA if %Z is less than 4% or 15 kVA if %Z is less than 2%.

  • How are Seismic Units Rated?

      Category:

      Tags: regulation, tests

      Three criteria are typically defined for seismic units:  Sds, Ip, z/h.

      Sds = Design earthquake spectral response acceleration parameter at short periods (ASCE 7-16 Section 11.4.4 Design Spectral Acceleration Parameters).  The required motion coefficient is dependent on the facility’s location and soil type. Most of the United States requires Sds = 0.05 to 1.5g. Specific regions require an Sds = 2.0g such as along the Missouri state line south of Illinois and parts of California.

      Ip = Component Importance Factor (ASCE 7-16 Section 13.1.3 Component Importance Factor).  Ip is dependent on the function of the building in which the transformer is installed. Typically, an Ip is assumed to equal 1.5 for transformers expected to function continuously through and after an earthquake.

      z/h = A ratio of the height in the structure that the component has been anchored, to the overall height of the structure.  A value of z/h of 1.0 states that the component is capable of being installed anywhere within the structure (ASCE 7-16 Section 13.3.1 Seismic Design Force).

      z/h - a ratio of the height of the structure

  • What is Seismic Certified?

      Category:

      Tags: regulation, tests

      A fair amount of construction projects require components to be “Seismic Certified.” A Seismic Certification ensures the component will withstand and operate after an event such as an earthquake. In addition to requiring structural components to meet specific seismic regulations, most jurisdictions also require non-structural components – including electrical systems – to be “Seismic Certified.”

      Seismic requirements are defined by the International Building Code 2018 and the California Building Code (2019). ASCE 7-16 is the base standard for many building codes, and is referenced by both IBC and the CBC.

      OSHPD, the Office of State-wide Health Planning and Development, requires actual “shake-testing” of products prior to allowing products to be specified for construction or retrofit projects anywhere in the state of California. This testing must be reviewed by a California state certified structural engineer. Without a widespread nationwide approval process, many other jurisdictions require the OSHPD Special Seismic Certification Preapproval (OSP) for projects.

  • What is a Secondary Winding?

      Category:

      Tags: winding

      The transformer winding connected to the load or output side (customer end).

  • What is a Ratio Test?

      Category:

      Tags: ratio

      A test that is used to ensure the correct number of turns on the primary and secondary windings.  When the resulting ratio of turns between the primary and secondary windings is applied to the secondary winding phase voltage, you should arrive back at the primary phase voltage.

  • What is Ratio in terms of Voltage?

      Category:

      Tags: ratio

      In terms of voltage, the ratio of a transformer can be viewed from the primary side (the ratio of the primary voltage to the secondary voltage), or inversely from the secondary side (the secondary voltage to the primary voltage).

  • What is a Primary Winding?

      Category:

      Tags: winding

      The primary winding is the winding on the energy input (supply) side.

  • What are Primary Taps?

      Category:

      Tags: taps

      Primary taps are additional terminals added to the primary winding that allows the customer to apply different supply voltages.  Primary taps can be provided as FCBN (Full capacity Above Nominal), or FCBN (Full Capacity Below Nominal).  The taps are generally below or above the nominal rated primary voltage in specific percentage increments provided by the customer.

  • How are single phase and three phase load amps and load kVA calculated?

      Category:

      Tags: FAQ

      Single phase Amps = (kVA x 1000)/Volts

      Three phase Amps = (kVA x 1000)/Volts x 1.73

      Single phase KVA = (Volts x Amps)/1000

      Three phase KVA = (Volts x Amps x 1.73)/1000

  • What is a Harmonic?

      Category:

      Tags: harmonics

      A sinusoidal component of a periodic wave having a frequency that is a multiple of the fundamental frequency. A component whose frequency is twice the fundamental frequency is referred to as the 2nd harmonic, (120 Hz is the 2nd harmonic of 60 Hz).

      It is recommended that transformers which experience high harmonic levels be specified with a K-rating.

  • Do dry type transformers require a Spill Prevention, Control and Countermeasure (SPCC) plan per 40 CFR part 112?

      Category:

      Tags: insulation

      A Spill Prevention, Control and Countermeasure (SPCC) plan per 40 CFR part 112 is typically required for many liquid cooled transformer installations. The purpose of the Spill Prevention, Control, and Countermeasure (SPCC) rule is to help facilities prevent a discharge of oil into navigable waters or adjoining shorelines. Dry type transformers do not require an SPCC plan.

  • Does HPS build network transformers?

      Category:

      Tags: FAQ

      Network Transformers typically range from 300 kVA to 2,500 kVA three-phase. The Primary voltage ranges from 2400 VAC to 34,500 VAC and the secondary from 600VAC to 208 VAC. The type may be oil, dry (VPI) or cast-coil. The primary is usually delta connected, and the secondary is wye connected. The high-voltage connection is usually to a network switch or an interrupter-type switch. The secondary connection is usually to a network protector or a low-voltage air circuit breaker.

      HPS can provide both VPI and Cast Coil Secondary Unit Network Transformers. There is a type of Network transformer often called a subway type. This is installed in a vault and used in areas where they are occasionally or frequently submerged in water, HPS does not currently offer this type of system.

  • Do different types of non-linear loads generate different harmonics?

      Category:

      Tags: harmonics, three phase

      By far the majority of today’s non-linear loads are rectifiers with DC smoothing capacitors. These rectifiers typically come in 3 types:
      (i) single phase, line-to-neutral
      (ii) single phase, phase-to-phase
      (iii) three-phase

      Single-phase line-to-neutral rectifier loads, such as switch-mode power supplies in computer equipment, generate current harmonics 3rd, 5th, 7th, 9th and higher. The 3rd will be the most predominant and typically the most troublesome. 3rd, 9th and other odd multiples of the 3rd harmonic are often referred to as triplen harmonics and because they add arithmetically in the neutral are also considered zero sequence currents. Line-to-neutral non-linear loads can be found in computer data centers, telecom rooms, broadcasting studios, schools, financial institutions, etc.

      208V single-phase rectifier loads can also produce 3rd, 5th, 7th, 9th and higher harmonic currents but if they are reasonably balanced across the 3 phases, the amplitude of 3rd and 9th will be small. Because they are connected line-line, these loads cannot contribute to the neutral current. The largest current and voltage harmonics will generally be the 5th followed by the 7th. Typical single phase, 208V rectifier loads include the switch-mode power supplies in computer equipment and peripherals.

      Three-phase rectifier loads are inherently balanced and therefore generally produce very little 3rd and 9th harmonic currents unless their voltage supply is unbalanced. Their principle harmonics are the 5th and 7th with 11th and 13th also present. They cannot produce neutral current because they are not connected to the neutral conductor. The rectifiers of variable speed drives and Uninterruptible Power Supplies (UPS) are typical examples of three-phase rectifier loads.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What is a Harmonic Mitigating Transformer and how is it different than a K-Rated Transformer?

      Category:

      Tags: harmonics, Wye

      Harmonic Mitigating Transformers, or HMTs, are specifically designed to minimize the voltage distortion and power losses that result from the harmonics generated by non-linear loads such as personal computers. The accomplish this through the use of a zig-zag winding.

      K-rated transformers, on the other hand, are simply designed to prevent their overheating when subjected to heavy non-linear loading, but do very little to reduce the harmonic losses themselves. And as for voltage distortion, K-rated transformers perform the same as conventional general purpose delta-wye transformers.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What is the difference between a Variable Frequency Drive’s (VFD) fundamental frequency and the VFD’s carrier (switching) frequency?

      A VFD’s fundamental frequency is the frequency of the output current, typically >0 to 400HZ for most VFD’s. This frequency determines the speed of the motor and is simulated by the drive’s higher carrier frequency output.

      The VFD’s Carrier (Switching) frequency is the frequency of the PWM (Pulse Width Modulation) pulses, i.e. the frequency at which the VFD’s output transistors; usually IGBTs (Insulated Gate Bipolar Transistors), are switching. This typically ranges from 2 to 20 kHz. This high frequency PWM current output simulates a lower frequency sine wave and provides the drive’s variable fundamental frequency output.

  • Define VPI Impregnation?

      Category:

      Tags: VPI

      A vacuum and pressure impregnation process using a resin that is then oven cured to completely seal and protect the surface of a transformer and provides a strong mechanical bond. This process is standard on all HPS transformer products.

  • Define Series/Multiple?

      Category:

      Tags: winding

      A winding consisting of two or more sections which can be connected for series operation or multiple (parallel) operation. Also referred to as dual voltage or series-parallel.

  • What is a dual output Harmonic Mitigating Transformer?

      Category:

      Tags: harmonics, winding

      Like a standard HMT, a dual put HMT minimizes the voltage distortion rise due to the transformer itself. Harmonic Mitigating Transformers (HMTs) are designed to reduce the impedance seen by the harmonic currents. This is accomplished through zero sequence flux cancellation and through phase shifting. The secondary winding configuration of the HMT cancels the zero sequence fluxes; those produced by the 3rd, 9th, 15th (triplen) current harmonics, without coupling them to the primary windings.

      This prevents the triplen current harmonics from circulating in the primary windings as they do in a delta-wye transformer. The flux cancellation also results in much lower impedance to the zero sequence currents and hence lower voltage distortion at these harmonics. In addition, the reduced primary winding circulating current will lower losses and allow the transformer to run cooler.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • Can a damaged coil be repaired, refurbished or replaced?

      Category:

      Tags: overload, performance

      Low and medium voltage coils which have been damaged can be repaired, refurbished or replaced. Repairing involves fixing the issue without removing the coil from the core. This may be an option for transformers which have sustained much physical damage or if an issue such as lowering insulation levels is diagnosed before actual failure. This may also be possible for transformers which are dirty or have been submerged. In some cases the the coil can be removed and refurbished. This would typically be done for larger, often medium voltage transformers which have sustained damage to the outer, primary winding. The last option is to replace the coil entirely which is often done if the coil is severely damage, the inner winding is damaged or the transformer can’t be sufficiently cleaned.

      While coils can be repaired, refurbished and replaced, this must be compared to the cost of providing a new unit. Repairs must factor in additional transportation and testing costs, higher disassembly and assembly costs, core damage and replacement and the benefits of using a new transformer, often with modern higher efficiencies. Repair is often only practical for large custom transformers.

  • Can a Scott-T connected transformer be fed to go from two phases to three phases?

      Category:

      Tags: three phase

      In theory, you can feed a Scott-T connected transformer with two phase power and derive three phases. However, the two phase feed would need to have the two phases offset by 90 degrees. In practicality, there are no two phase generators on the market that can provide this feed.

      In some cases, this is discussed with an open delta system. Since an open delta system does not have the two phases offset by 90 degrees, a Scott T connected transformers can not be used in this application.

  • Can a Scott-T connected transformer be fed from two phases of an open delta system to create a three phase system?

      Category:

      Tags: three phase

      No. The two phase input of a Scott-T connected transformer requires the two phases to be offset by 90 degrees. Since an open delta system does not have the two phases offset by 90 degrees, a Scott-T connected transformer can not be used in this application. There are currently no practical magnetics solutions to this application.

  • When is audible sound level an issue in the design?

      Category:

      Tags: sound level

      Sound needs to be considered when transformers are located in close proximity to occupied areas. All energized transformers emanate sound due to the alternating flux in the core. The larger the kVA, the louder the audible noise. This normal sound emitted by the transformer can be a source of annoyance unless it is kept below acceptable levels. There are ways of minimizing sound emission as discussed in the HPS “Field Service Guide”.

      HPS Transformers are built to meet the latest ANSI, CSA and UL standards. Audible noise is typically define by NEMA ST-20.

  • Are Harmonic Mitigating Transformers (HMT’s) available in medium voltage configurations?

      Yes, Harmonic Mitigating Transformers are available as an option from HPS in medium voltage VPI and Cast Coil designs.

  • Are electrical systems safe from harmonics if K Rated transformers?

      Category:

      Tags: harmonics

      K-Rated transformers made their appearance several decades ago as a means of preventing transformers from failing when subjected to heavy non-linear loading. They are essentially ‘beefed up’ transformers with extra steel in their cores and conductors in their windings to allow for better dissipation of the excessive losses produced by harmonic currents. K-Rated transformers are not designed to cancel harmonics or their fluxes and therefore, do nothing but protect themselves from overheating.

      Harmonic losses are normally not significantly reduced and voltage distortion will typically remain quite high under more heavily loaded conditions. To improve power quality in the form of reduced voltage distortion and to save energy costs, the use of a transformer designed to cancel harmonics is necessary.

      Over-sizing neutrals, on the other hand, can be a reasonably low cost method for the prevention of neutral conductor overheating. It is important to remember that the non-linear loads are the source of the harmonic currents. They must flow from the loads back to the transformer. Because the 3rd and 9th current harmonics created by the 120 VAC switch-mode power supplies are flowing back on the neutral, the neutral current is usually larger than the phase currents. This is of minimal consequence provided the neutral has suitable ampacity to carry the extra current and the 120/208V 4-wire run length is not too long.

      When selecting phase and neutral conductor sizes in a non-linear load application, the electrical code requires that an ampacity adjustment or correction factor be applied. This is because the neutral conductor is considered to be a current carrying conductor along with Phase A, Phase B and Phase C. With more than 3 current carrying conductors in a conduit or raceway, a 0.8 factor must be applied.

      To minimize harmonic problems in new installations, avoid the old approach of using a large central transformer with a 120/208V secondary and long 4-wire risers or radial runs through the building. The impedances of these long runs are high so that harmonic currents flowing through these impedances will create high levels of voltage distortion and neutral-to-ground voltage. To prevent these problems, an effective rule of thumb is to limit each 120/208V run length to that which would produce a 60Hz voltage drop not greater than 1/2% to 3/4%. For a typical 200 amp feeder this would be < 50 ft.

      Combining the use of Harmonic Mitigating Transformers with short 120/208V feeder runs and double ampacity neutrals will ensure compatibility between the distribution system and the non-linear loads. Generally this will keep voltage distortion safely below the maximum of 5% as recommended for sensitive loads in IEEE Std 519-2014.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What does ANN mean?

      Category:

      Tags: heat

      “Air Natural Convection Cooling” – Natural convection circulates air through a dry-type transformer to cool the unit.

  • What does ANN/AFN mean?

      Category:

      Tags: heat

      “Air Natural Convection Cooling plus Forced Air Cooling” – Fans force more air to circulate through a dry-type transformer to cool the unit typically adding 33% additional capacity verses a similar non-fan cooled unit.

  • What does ANC mean?

      Category:

      Tags: heat

      “Air Natural Convection Total Enclosed” – The dry-type transformer is enclosed in a non-ventilated enclosure.  Heat is transferred through the sides of the enclosure to the air to cool the unit.

  • What does the abbreviation NEMA refer to?

      Category:

      Tags: NEMA

      National Electrical Manufacturers Association.

  • Do HPS transformers conform to the NEC 451-10 grounding requirements?

      Category:

      Tags: regulation

      All HPS enclosed transformers and reactors can be installed to be compatible with the NEC 451.10 grounding requirements.

      A) Dry-Type Transformer Enclosures. Where separate equipment grounding conductors and supply-side bonding jumpers are installed, a terminal bar for all grounding and bonding conductor connections shall be secured inside the transformer enclosure. The terminal bar shall be bonded to the enclosure in accordance with 250.12 and shall not be installed on or over any vented portion of the enclosure.

      Exception: Where a dry-type transformer is equipped with wire-type connections (leads), the grounding and bonding connections shall be permitted to be connected together using any of the methods in 250.8 and shall be bonded to the enclosure if of metal.

      HPS ventilated low-voltage transformers are typically supplied with pre-installed grounding bars or lugs. If the unit does not have pre-installed lugs, the enclosure is compatible for the user to install the required lugs in accordance with NEC 250.12. It is the installer’s final responsibility to determine if the final installation complied with local code requirements.

  • What is the duty cycle of a transformer?

      Duty cycle is the amount of load over set periods of time. Transformers are designed to run continuously at full load without exceeding the insulation temperature limits provided that parameters such as ambient temperature, harmonic distortion, power factor, etc., are met. Transformers can also be designed to run for short term duty cycles which may result in a smaller unit. Short term duty cycles will need lower or no-load periods to aid in cooling. High load duty cycles can affect parameters such as impedance and voltage regulation.

  • What is the effect of “Overload”?

      Category:

      Tags: overload

      Overload is when a transformer is subjected to voltages and/or currents that exceed its design specifications. During overloading conditions, excess heat will cause the insulation system to break down, resulting in decreased life expectancy of the transformer.

  • What are the overload capacities of cast coil transformers?

      Category:

      Tags: cast coil, overload

      Cast coil transformers typically come with two insulation systems. 155C is common for IEC rated transformers while 185C is required for U.L. listed units. The 185C insulation system offers additional overload ratings over the 155C system. Assuming a maximum ambient of 40C and average of 30C, a 185C insulation system is typically rated at 115C temperature rise. When built with a 100C temperature rise, the unit will have an overload capacity of 6%. At an 80C temperature rise, the unit will have an overload capacity of 17%.

      A cast coil transformer using a 155C base insulation system has a base 80C temperature rise. So, at 80C, there would be no additional overload capacity.

  • What are the advantages and disadvantages of an open delta transformer configuration ?

      Category:

      Tags: single phase

      Open-delta configurations are typically deployed by utilities, typically to loads with little single-phase requirements.

      Advantages:

      • Open-deltas only require the utility to install two transformers.
      • Future Capacity can be increased by simply installing a third similar sized transformer verses installing 2-3 larger transformers.

      Disadvantages:

      • While the line to line voltages will be equal, the line to neutral voltages will have two phases being equal and one phase being 1.732 times larger.
      • Unbalanced single phase loads can cause voltage fluctuations and additional, uneven transformer heating.
      • An open delta connection only has 58% of the capacity of a full set of three transformers, that is a 42% decrease in actual capacity event though the installed capacity only drops by 33%.

       

  • What are non-linear loads and why are they a concern today?

      Category:

      Tags: non-linear

      A load is considered non-linear if its impedance changes with the applied voltage. The changing impedance means that the current drawn by the non-linear load will not be sinusoidal even when it is connected to a sinusoidal voltage. These non-sinusoidal currents contain harmonic currents that interact with the impedance of the power distribution system to create voltage distortion that can affect both the distribution system equipment and the loads connected to it.

      In the past, non-linear loads were primarily found in heavy industrial applications such as arc furnaces, large variable speed drives, heavy rectifiers for electrolytic refining, etc. The harmonics they generated were typically localized and often addressed by knowledgeable experts.

      Times have changed. Harmonic problems are now common in not only industrial applications but in commercial buildings as well. This is due primarily to new power conversion technologies, such as the Switch-Mode Power Supply (SMPS), which can be found in virtually every power electronic device (computers, servers, monitors, printers, photocopiers, telecom systems, broadcasting equipment, electric vehicle chargers, etc.). The SMPS is an excellent power supply, but it is also a highly non-linear load. Their proliferation has made them a substantial portion of the total load in most commercial buildings.

      More Harmonic Mitigating Transformer Frequently Asked Questions

  • What are Insulating Materials?

      Category:

      Tags: insulation

      Those materials used to electrically insulate the transformer’s windings, turn-to-turn or layer-to-layer, and other assemblies in the transformer such as the core and busswork.  Nomex, polyester, epoxy, rubber, Glastic and plastic are commonly used as insulating materials in the electrical industry.

  • What is considered Low Voltage for distribution transformers?

      Category:

      Tags: low voltage

      The term “Low Voltage” for electrical distribution transformers can refer to different voltages. Generally transformers with primary and secondary voltages at or below 600 volts are considered “Low Voltage”.

      • 690 Volts is sometimes considered low voltage. It is sometimes referred to as a 600/690 volt system.
      • The National Electric Code considers voltages <1000 volts to be low voltage.
      • Some regulatory agencies consider 1.2 kV and below to be low voltage.

      As a result there is some market confusion for voltages between 600 and 1200 volts with some regulations having a definition gap for some of these voltages.

  • Are “Low Temperature Rise” transformers more efficient?

      One common misconception is that low temperature rise units are more efficient.

      While they usually have better efficiency at full load, it doesn’t guarantee that this will be the case at lower loads.

      Efficiency regulations typically use an average load of 35% to 50% when specifying efficiency. A low temperature rise transformer with more mass and surface area, but running with a low load may be less efficient and produce more heat than a standard transformer, while still maintaining a low overall temperature rise.

      Core loss for low temperature rise units are higher than a transformer with the same kVA rating, but a higher rise (present whenever unit is energized).

      Transformer temperature rise and efficiency should be regarded as two separate issues. If a high efficiency unit is desired, the TP1 (DOE 10 CFR Part 431), C802.2 (Canada) or NEMA Premium® energy efficient specifications should be noted. These regulations are all compatible with low temperature rise transformers.

  • What are Load Losses?

      Category:

      Tags: loss

      They are losses in a transformer, which are incident to load carrying. Load loses include I2R loss in the windings due to load current, stray loss due to stray fluxes in the windings, core clamps, etc., and to circulating currents (if any), in parallel windings

  • What does the abbreviation KVA stand for?

      Category:

      Tags: FAQ

      “Kilovolt Ampere Rating” designates the output that a transformer can deliver for a specified time at rated secondary voltage and rated frequency without exceeding the specified temperature rise. (1 kVA = 1000 VA, or 1000 volt amperes)

  • What is an Isolation Transformer?

      Category:

      Tags: isolation

      Practically all transformers (with the exception of Autotransformers) are, in fact, Isolation Transformer.  This is due to the fact that their primary and secondary windings are PHYSICALLY isolated from each other (they are not physically connected to each other).  The transformation in voltage and current between primary and secondary windings occurs as a result of the shared magnetic field in the core (Mutual Inductance).

  • Is ice snow or frost conductive?

      Category:

      Tags: performance

      Yes, ice, snow and frost are conductive and should be considered in the same terms as the liquid form of water. If ice, snow or frost come into contact with energized parts of a transformer, a fault and damage can occur. If a fault doesn’t occur initially, the heat from an energized transformer will cause ice, snow and frost to melt which can further increase the chances of a damaging fault occurring.

  • What is an Earthing Transformer?

      Category:

      Tags: grounding

      An “Earthing Transformer” is another name for a grounding transformer.

  • Insulating Materials, what are they made of and what is their purpose?

      Category:

      Tags: insulation

      HPS utilizes Mylar, Nomex and other high-quality insulating materials.  These materials are used to provide insulation throughout many areas of a transformer so as to prevent failure between components having different voltage potentials (for example, Core to Ground).

  • Can I increase the efficiency of an existing transformer?

      There are two main loss area of a transformer, load losses in the coils and no-load losses in the core. Coil losses can only be lowered by completely replacing the coils and using a larger conductor which typically would not be compatible with existing core. In order to reduce core losses, better grades of steel and/or more advanced core design would require the complete replacement of the core while still reusing the coils. While possible,